Features

  • Fully Approved Explosion-Proof Pulse Input Flow Rate/Totalizers
  • Dual Pulse, Open Collector, NPN, PNP, TTL, Switch Contact, Sine Wave (Coil), Square Wave Inputs
  • Rate, Total, and Grand Total for Each Input Channel
  • Display Rate & Total at the Same Time
  • Dual-Line 6-Digit Display, 0.6" (15 mm) & 0.46" (12 mm)
  • SafeTouch Through-Glass Button Programming
  • Display Mountable at 0°, 90°, 180°, & 270°
  • Isolated 5, 10 or 24 VDC Flowmeter Power Supply
  • Gate Function for Display of Slow Pulse Rates
  • 4 Relays with Interlocking Capability + Isolated 4-20 mA Output Option
  • Free PC-Based, On-Board, MeterView Pro USB Programming Software
  • SunBright Display Standard Feature; Great for Outdoor Applications
  • Total, Grand Total or Non-Resettable Grand Total
  • Front Panel or Remote Total Reset
  • Password Protection for Programming and Total Reset
  • Total Stored in Non-Volatile Memory
  • K-Factor, Internal Scaling, or External Calibration
  • Operating Temperature Range: -55 to 65°C (-67 to 149°F)
  • CSA Certified as Explosion-Proof / Dust-Ignition-Proof / Flame-Proof
  • ATEX and IECEx Certified as Dust-Ignition-Proof / Flame-Proof
  • Input Power Options: 85-265 VAC / 90-265 VDC or 12-24 VDC / 12-24 VAC
  • Programmable Display, Function Keys & Digital Inputs
  • Flanges for Wall or Pipe Mounting
  • Explosion-Proof Aluminum or Stainless Steel NEMA 4X / IP68 Enclosures
  • On-Board RS-485 Serial Communications
  • Modbus RTU Communication Protocol Standard
  • Four 3/4" NPT Threaded Conduit Openings
  • 3-Year Warranty

Overview

Front

PD8-6363 Front

Connections

PD8-6363 Connections

Introduction

The ProtEX-MAX PD8-6363 is an explosion-proof dual pulse input rate/totalizer ideal for flow rate, total, and flow control applications. The totalizer features a dual-line display, with a main display of 0.60" (15 mm) high, and a second display of 0.46" (12 mm) high superluminous LED digits, which can be read in any lighting condition, including direct sunlight. The totalizer is housed in a field-mountable, NEMA 4X/IP68 rated enclosure available in either aluminum or stainless steel for convenient indoor and outdoor installation.

The totalizer accepts a wide variety of pulse signals from two (2) pulse output flowmeters that can be displayed as flow rate, total and grand total. The rates, as measured by the flowmeters, are automatically aggregated into cumulative totals and grand totals which can be displayed with the rates.

Various math functions may be applied to the rate, total, and grand total of the two channels, including addition, difference, absolute difference, average, weighted average, multiplication, division, minimum, maximum, draw, ratio, and concentration.
The displays, relays, and the analog output may be assigned to the rate, total, or grand total of input channels A or B, or math result channel C. Three of the programming buttons can be set for custom operation.

A fully loaded ProtEX-MAX PD8-6363 dual-input flow rate/totalizer comes with four SPDT relays, a 4-20 mA output, five digital inputs and four digital outputs, and RS-485 serial communications. The four relays can be used for alarm indication or process control applications. The 4-20 mA isolated output, Modbus RTU serial communications, and digital I/O features make the ProtEX-MAX an excellent addition to any system.

General

Display: Upper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. 6 digits each (-99999 to 999999), red LEDs with lead zero blanking.
Display Intensity: Eight user selectable intensity levels
Display Update Rate: 10 per second; up to 1 per 100 seconds (and is a function of Low Gate setting); Total: 10 per second (fixed)
Overrange: Display flashes 999999
Underrange: Display flashes -99999
Display Assignment: The Upper and Lower displays may be assigned to show: One or more rate channels: Channel A (Ch-A), B (Ch-B), or C (Ch-C), Toggle between rate channels: Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C, Total or grand total: Ch-A or Ch-B, Rate and total or grand total: Ch-A, Ch-B, Relay set points, Max and/or min values: Ch-A, Ch-B, or Ch-C, Toggle between any rate channel & units, Toggle between any rate/math channel & units, Total and units: Ch-A or Ch-B, Toggle between totals: Ch-A & Ch-B; Ch-A, Ch-B, and sum of Ch-A and Ch-B, Modbus input. The lower display may also be set to show engineering units or be off, with no display.
Programming Methods: Four through-glass SafeTouch buttons, four mechanical buttons behind glass, digital inputs, PC and MeterView Pro software, or Modbus registers.
F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC; Logic Low: 0 to 1.25 VDC
Max/Min Display: Max/min readings reached by the process are stored until reset by the user or until power to the meter is cycled.
Password: Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals.
   Pass 1: Allows use of function keys and digital inputs
   Pass 2: Allows use of function keys, digital inputs and editing set/reset points
   Pass 3: Restricts all programming, function keys, and digital inputs.
   Total: Prevents resetting the total manually
   Gtotal: Prevents resetting the grand total manually
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max, or optional model with 12-24 VDC ±10%, 15 W max.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 10%. Isolated from the input at >500 V. Jumper selectable for 24, 10, or 5 VDC supply (internal jumper J4). All models transmitter supply rated @ 25mA max.
Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
Overvoltage Category: Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Environmental:
T6 Class operating temperature range Ta = -55 to 60°C
T5 Class operating temperature range Ta = -55 to 65°C
Storage temperature range: -55 to 85ºC (-67 to 185ºF)
Relative humidity: 0 to 90% non-condensing
Max Power Dissipation: Maximum power dissipation limited to 15.1 W.
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Mounting: Four slotted flanges for wall mounting or NPS 1½" to 2½" or DN 40 to 65 mm pipe mounting
Dimensions: 6.42" x 7.97" x 8.47" (W x H x D) (163 mm x 202 mm x 215 mm)
Weight:
Aluminum: 14.7 lbs (6.67 kg)
Stainless Steel: 23.5 lbs (10.66 kg)
Warranty: 3 years parts & labor
USB Connection: Compatibility: USB 2.0 Standard, Compliant
   Connector Type: Micro-B receptacle
   Cable: USB A Male to Micro-B Cable
   Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit,
   Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
   Power: USB Port

 

Dual Input Functionality

Pulse Inputs: Two, Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 kΩ pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7Ω kpull-up to 5 V @ 40 Hz; Modbus PV (Slave) Channels: Channel A, Channel B, Channel C (Math channel)
Programmable Constants: Constant P (Adder): -99.999 to 999.999, default: 0.000, Constant F (Factor): 0.001 to 999.999, default: 1.000
Sequence of Operations for Input Programming:
   1.  Select Input for A and B
   2.  Set up the rate, total, and grand total engineering units for channels A & B, and units for math channel C
   3.  Set up rate, total, and grand total decimal points for channels A & B, and decimal point for math channel C
   4.  Program channel A & B rate parameters
   5.  Program channel A & B total and reset parameters
   6.  Set up the big and little displays and display intensity
   7.  Select the transfer function for A & B (e.g. Linear)
   8.  Select Math function for Channel C
   9.  Program constants for Factor (F) and Adder (P)
   10. Program cutoff values for A and B
Low Voltage Mag Pickup: Sensitivity: 40 mVp-p to 8Vp-p
Minimum Input Frequency: 0.001 Hz Minimum frequency is dependent on high gate setting.
Maximum Input Frequency: 30,000 Hz (10,000 for low voltage mag pickup)
Accuracy: ±0.03% of calibrated span ±1 count
Temperature Drift: 0.005% of calibrated span/°,C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 07°C ambient Rate display is not affected by changes in temperature.
Multi-Point Linearization: 2 to 32 points for channel A and B
Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd.
Calibration Range: Input 1 signal may be set anywhere in the range of the meter; input 2 signal may be set anywhere above or below input 1 setting. Minimum input span between any two inputs is 10 Hz. An error message will appear if the input span is too small.
Calibration: May be calibrated using K-factor, internal calibration, or by applying an external calibration signal.
K-Factor: Field programmable K-factor converts input pulses to rate in engineering units. May be programmed from 0.00001 to 999,999 pulses/unit.
Filter: Programmable contact de-bounce filter: 40 to 999 Hz maximum input frequency allowed with low speed filter.
Time Base: Second, minute, hour, or day
Gate: Low gate: 0.1-99.9 seconds, High gate: 2.0-999.9 seconds
F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC, Logic Low: 0 to 1.25 VDC

 

Dual Rate/Totalizer

Rate Display Indication: 0 to 999999, lead zero blanking.
Total Display & Total Overflow: 0 to 999,999; automatic lead zero blanking. Up to 999,999,999 with total-overflow feature. "oF in 7-Segment Font" is displayed to the left of total overflow.
Total Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd. Total decimal point is independent of rate decimal point. Channel A and B decimal points programmed independently.
Dual Totalizer: Calculates total for channels A and B based on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed. Channel A and B totalizer parameters programmed independently.
Totalizer Rollover: Totalizer rolls over when display exceeds 999,999,999. Relay status reflects the display value.
Total Overflow Override: Program total A or B total reset for automatic with 0.1 second delay and set point 1 for 999,999
Totalizer Alarm Presets: Up to eight, user selectable under setup menu. Any set point can be assigned to channel A or B total or grand total (or C) and may be programmed anywhere in the range of the meter for total alarm indication.
Total & Grand Total Reset: Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications. Channel A and B total and grand total reset parameters programmed independently.
Total Reset Password: Total and grand total passwords may be entered to prevent resetting the total or grand total from the front panel.
Non-Resettable Total: The grand totals can be programmed as non-resettable totals by entering the password "050873". Both channels are set to non-resettable when this password is entered. Caution: Once the Grand Total has been programmed as "non-resettable" the feature cannot be disabled.
Programmable Delay on Release: 0.1 and 999.9 seconds; applied to the first relay assigned to total or grand total. If the meter is programmed to reset total to zero automatically when the preset is reached, then a delay will occur before the total is reset.

 

Relays

Rating: 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads
Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads.
Relay Assignment: Relays may be assigned to channel A or B rate, total, or grand total; channel C; or Modbus control.
Deadband: 0-100% of span, user programmable
High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
Relay Operation: automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), off (disable unused relays), and manual on/off control mode.
Relay Reset: User selectable via front panel buttons, digital inputs, or PC
   1. Automatic reset only (non-latching), when input passes the reset point.
   2. Automatic + manual reset at any time (non-latching).
   3. Manual reset only, at any time (latching).
   4. Manual reset only after alarm condition has cleared (latching).
Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.
Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
Fail-Safe Operation: Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.

 

 

Isolated 4-20 mA Transmitter Output

Output Source: Input channels A or B, rate, total, or grand total; channel C; max or min for channel A or B; highest or lowest max or min of A and B; set points 1-8; Modbus input; or manual control mode.
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated: 4.000 to 20.000 = 4-20 mA output
Analog Output Programming: 23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
Accuracy: ±0.1% FS ±0.004 mA
Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models @ 25 mA max.
External Loop Power Supply: 35 VDC maximum
Output Loop Resistance:

 

      Power supplyMinimumMaximum
      24 VDC10Ω700Ω
      35 VDC (external)100Ω1200Ω

Serial Communications

Compatability: EIA-485
Connectors: Removable screw terminal connector
Max Distance: 3,937' (1,200 m) max
Status Indication: Separate LEDs for Power (P), Transmit (TX), and Receive (RX)
Protocol: Modbus® RTU
Meter Address/Slave ID: 1 - 247
Baud Rate: 300 - 19,200 bps
Transmit Time Delay: Programmable between 0 and 199 ms
Data: 8 bit (1 start bit, 1 or 2 stop bits)
Parity: Even, odd, or none with 1 or 2 stop bits
Byte-to-Byte Timeout: 0.01 - 2.54 seconds
Turn Around Delay: Less than 2 ms (fixed)

 

Digital Inputs and Outputs

Channels: 4 digital inputs & 4 digital outputs per module
System: One expansion module may be added for a total of 8 inputs & 8 outputs
Note: The jumper located between the RJ45 connectors must be removed on the expansion module.
Digital Input Logic: High: 3 to 5 VDC; Low: 0 to 1.25 VDC
Digital Output Logic: High: 3.1 to 3.3 VDC; Low: 0 to 0.4 VD
Source Current: 10 mA maximum output current
Sink Current: 1.5 mA minimum input current
+5 V Terminal: To be used as pull-up for digital inputs only. Connect normally open pushbuttons across +5 V & DI 1-4. Warning: DO NOT use +5 V terminal (pin 1) to power external devices.
Function Assignment: The on-board digital inputs (1-4) are designed to mimic the behavior of the front panel buttons (Menu, F1, F2, & F3). If you wish to change their behavior, re-assign F1-F3 to the desired function, then change the corresponding digital input to match.

 


Enclosure

Material-AL Models: ASTM A413 LM6 die-cast aluminum, copper-free, enamel coated
-SS Models: ASTM A743 CF8M investment-cast 316 stainless steel
GasketFluoroelastomer
RatingNEMA 4X, IP68 Explosion-proof
Color-AL: Blue
-SS: Silver
WindowBorosilicate glass
ConduitsFour ¾" NPT threaded conduit openings
Conduit Stopping PlugsSold separately
FlangesTwo built-in flanges for wall and pipe mounting.
Tamper-Proof SealCover may be secured with tamper-proof seal.
Overall Dimensions6.42" x 7.97" x 8.47" (W x H x D)
(163 mm x 202 mm x 215 mm)
WeightAluminum: 14.7 lbs (6.67 kg)
Stainless Steel: 23.5 lbs (10.66 kg)
ATEXFlameproof
ATEXII 2GD
Ex db IIC Gb
Ex tb IIIC Db
IP66/IP68
Tamb: -55°C to +85°C
Certificate No.: Sira 19ATEX1252U
IECExFlameproof and dust protection
Ex db IIC Gb
Ex tb IIIC Db
IP66/IP68
Tamb: -55°C to +85°C
Certificate No.: IECEx SIR 19.0075U
CSAClass I, Division 1, Groups A, B, C, D
Class II, Division 1, Group E, F, G
Class III
Ex db IIC Gb
Ex tb IIIC Db
Class I, Zone 1, AEx db IIC Gb
Zone 21, AEx tb IIIC Db
IP66/IP68/TYPE 4X
Tamb: -55°C to +85°C
Certificate No.: 80011200
ULClass I, Division 1, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class III
Class I, Zone 1, AEx db IIC Gb
Zone 21, AEx tb IIIC
Ex db IIC Gb
Ex tb IIIC Db
IP66/IP68/TYPE 4X
Tamb: -55°C to +85°C
Certificate Number: E518920
Note: The above approvals are for the enclosure only. See below for approvals on the entire instrument.


General Compliance Information

Electromagnetic Compatibility

EmissionsEN 55022
Class A ITE emissions requirements
Radiated EmissionsClass A
AC Mains Conducted EmissionsClass A
ImmunityEN 61326-1
Measurement, control, and laboratory equipment
EN 61000-6-2
EMC heavy industrial generic immunity standard
RFI - Amplitude Modulated80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast Transients±2kV AC mains, ±1kV other
Electrostatic Discharge±4kV contact, ±8kV air
RFI - Conducted10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge±2kV Common, ±1kV Differential
Surge1KV (CM)
Power-Frequency Magnetic Field30 A/m 70%V for 0.5 period
Voltage Dips40%V for 5 & 50 periods
70%V for 25 periods
Voltage Interruptions<5%V for 250 periods
Note: Testing was conducted on meters with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.


Product Ratings and Approvals

CSAClass I, Division 1, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1, T5
Class III, Division 1, T6 (Ta max = 60°C)
Ex db IIC T5
Ex db IIC T6 (Ta max = 60°C)
Ex tb IIIC T90°C
Ta = -55°C to +65°C
Enclosure: Type 4X & IP66 / IP68
CSA Certificate: CSA 12 2531731
ATEXII 2 G D
Ex db IIC T* Gb
Ex tb IIIC T90°C Db IP68
Ta = -55°C to +*°C
*T6 = -55°C to +60°C
*T5 = -55°C to +65°C
Certificate Number: Sira 12ATEX1182X
IECExEx db IIC T* Gb
Ex tb IIIC T90°C Db IP68
Ta = -55°C to +*°C
*T6 = -55°C to +60°C
*T5 = -55°C to +65°C
Certificate Number: IECEx SIR 12.0073X
ATEX/IECEx Specific Conditions of Use:
  1. The equipment label and epoxy coating may generate an ignition-capable level of electrostatic charges under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charges on non-conducting surfaces. Additionally, cleaning of the equipment should be done only with a damp cloth.
  2. Flameproof joints are not intended to be repaired.
  3. All entry closure devices shall be suitably certified as “Ex d”, “Ex t” and “IP66/68” as applicable. Suitable thread sealing compound (non-setting, non-insulating, non-corrosive, not solvent based, suitable for the ambient rating) must be used at the NPT conduit entries to achieve the IPx8 rating while maintaining the Ex protection concept.
Year of Construction

This information is contained within the serial number with the first four digits representing the year and month in the YYMM format.

For European Community:

The ProtEX-MAX must be installed in accordance with the ATEX directive 2014/34/EU, and the product certificate Sira 12ATEX1182X.

Dimensions

PD8-6000 Dimensions Front View

Front View

PD8-6000 Dimensions Side View

Side View

Applications


Differential Pressure Flow (PD6262)

The PD8-6262 can display flow rate and total by extracting the square root from the 4-20 mA signal from differential pressure transmitters. The user selectable low-flow cutoff feature gives a reading of zero when the flow rates drop below a user selectable value.

  • Display Flow Rate
  • User Selectable Low-Flow Cutoff
  • Only 2 Calibration Points Required


Open Channel Flow (PD6262)

The PD8-6262, in combination with ultrasonic level transmitters, makes for an easy and convenient way to measure and display open channel flow rates and totals in most weirs and flumes, and take periodic samples. All the user needs to do is enter the exponents for the weirs or flumes into the PD8-6262 and the PD8-6262 automatically raises the input signals to those powers. Sampling can be based on the total flow or the flow rate. Each channel's signal input conditioning is programmed independently.



Weir Flow Calculated Using Exponential Signal Input Conditioning


Convert Pulse to 4-20 mA (PD6363)

The PD8-6363 accepts pulse outputs from flowmeters and with the appropriate option installed, can convert the pulses to a 4-20 mA signal. The 4-20 mA signal can be programmed to correspond to either the flow rate or the total flow.

  • Use K-Factor or Multi-Point Scaling
  • ProVu Powers the Flowmeter
  • Up to 3 Analog Outputs
loader.gif