Select & Scale Input
-
Select Thermocouple or RTD Input
- Select & Scale a Voltage Input
-
|
Input Type |
Display |
Key |
m V |
0 to 100 |
|
|
-10 to 20
|
|
|
V O L T S
|
0-10
|
|
|
1-5
|
|
|
0.4-2.0
|
|
|
Press and hold Set/Ent for 3 seconds to enter the setup menu.
- Press Down three times to reach the lockout password,.
- Press Set/Ent to enter the lockout password (the default is 0).
- Press Down to access(Input Group).
- Press Set/Ent to access parameter(Input Type).
- Press Up to select the input type based off the following table.
Note: Changing a parameter setting will cause it to flash.
- Once the input type is selected, press Set/Ent to accept the input type.
- Press Set/Ent 3 times to access parameter(Decimal Point).
- Enter the digit location for the decimal point to display in the scaled value.
Example:
|
Display
|
|
Display
|
|
Display
|
|
Display
|
- Press Set/Ent to accept the decimal point location if changed.
- Press Set/Ent to access parameter(Input Scale High).
- Press Up, Down, and Left to set this parameter to the value to be displayed at the high range of the sensor input (set by parameter).
- Press Set/Ent to accept the high range scaling if changed.
- Press Set/Ent to access parameter(Input Scale Low).
- Press Up, Down, and Left to set this parameter to the value to be displayed at the low range of the sensor input (set by parameter).
- Press Set/Ent to accept the low range scaling if changed.
- Press and hold Set/Ent for 3 seconds to exit the setup menu.
- Select & Scale a 4-20 mA Input
|
The Nova VirtualMeter assumes a 22°C or 72°F ambient temperature while programmed for a temperature input. |