Virtual Meter Instructions

Main Menus

Program Relay Operations
  1. Set Up a High Alarm Relay
  2. Set Up for PID Relay Control
    Note: There are three alarm relays in the Nova Virtual Meter, Out1, Sub1, and Sub2. Set Up for all relays are similar. These instructions define the setup of standard relay Out1 as a PID time-proportional relay output.
    1. Press and hold Set/Ent for 3 seconds to enter the setup menu.
    2. Press Down three times to reach the lockout password,.
    3. Press Set/Ent to enter the lockout password (the default is 0).
    4. Press Down two times to access(Output Group).
    5. Press Set/Ent to access parameter.
    6. Press Down to set this parameter to.
    7. Press Set/Ent to accept the operation of the relay as PID controlled.
    8. Press Set/Ent 7 times to access parameter(Cycle Time).
    9. Press Up or Down to set the number of seconds for each time-proportional cycle of the PID controller relay.
    10. Press Set/Ent to accept the cycle time if changed.
    11. Press and hold Set/Ent for 3 seconds to exit the setup menu.
    12. Set Up for On/Off Relay Control.
  3. Set Up for On/Off Relay Control
The Nova VirtualMeter assumes a 22°C or 72°F ambient temperature while programmed for a temperature input.