Virtual Meter Instructions

Main Menus

Program Analog Outputs
  1. Set Up as 15 VDC Voltage Pulse PID Control
  2. Set Up as 4-20 mA PID Control
  3. Set Up as a Retransmitting Output
    1. Press and hold Set/Ent for 3 seconds to enter the setup menu.
    2. Press Down three times to reach the lockout password,.
    3. Press Set/Ent to enter the lockout password (the default is 0).
    4. Press Down two times to access(Output Group).
    5. Press Set/Ent two times to access parameter.
    6. Press Up to select(Retransmit).
    7. Press Set/Ent to accept selection.
    8. Press Set/Ent multiple times untilis selected.
    9. Press Down two times to access (Retransmit Group).
    10. Press Set/Ent to access parameter (retransmit type).
    11. To set up a PV retransmitting output:
      1. Verify the default setting of is . Change if required.
      2. Press Set/Ent to accept if changed.
    12. To set Up a SP retransmitting output:
      1. Press Up to select.
      2. Press Set/Ent to accept.
    13. Press Set/Ent to access parameter .
    14. Press Up, Down, and Left to set what value will retransmit 20 mA.
    15. Press Set/Ent to accept.
    16. Press Set/Ent to access parameter .
    17. Press Up, Down, and Left to set what value will retransmit 4 mA.
    18. Press Set/Ent to accept.
    19. Press and hold Set/Ent for 3 seconds to exit the setup menu.
  4. Set Up as a Loop Power Supply
The Nova VirtualMeter assumes a 22°C or 72°F ambient temperature while programmed for a temperature input.