Virtual Meter Instructions
Main Menus
Program Analog Outputs
Set Up as 15 VDC Voltage Pulse PID Control
Set Up as 4-20 mA PID Control
Set Up as a Retransmitting Output
Press and hold
Set/Ent
for 3 seconds to enter the setup menu.
Press
Down
three times to reach the lockout password,
.
Press
Set/Ent
to enter the lockout password (the default is 0).
Press
Down
two times to access
(Output Group).
Press
Set/Ent
two times to access parameter
.
Press
Up
to select
(Retransmit).
Press
Set/Ent
to accept selection.
Press
Set/Ent
multiple times until
is selected.
Press
Down
two times to access
(Retransmit Group).
Press
Set/Ent
to access parameter
(retransmit type).
To set up a PV retransmitting output:
Verify the default setting of
is
. Change if required.
Press
Set/Ent
to accept if changed.
To set
Up
a SP retransmitting output:
Press
Up
to select
.
Press
Set/Ent
to accept.
Press
Set/Ent
to access parameter
.
Press
Up
,
Down
, and
Left
to set what value will retransmit 20 mA.
Press
Set/Ent
to accept.
Press
Set/Ent
to access parameter
.
Press
Up
,
Down
, and
Left
to set what value will retransmit 4 mA.
Press
Set/Ent
to accept.
Press and hold
Set/Ent
for 3 seconds to exit the setup menu.
Set Up as a Loop Power Supply
The Nova VirtualMeter assumes a 22°C or 72°F ambient temperature while programmed for a temperature input.