Virtual Meter Instructions
Main Menus
Program Analog Outputs
Set Up as 15 VDC Voltage Pulse PID Control
Set Up as 4-20 mA PID Control
Set Up as a Retransmitting Output
Set Up as a Loop Power Supply
Press and hold
Set/Ent
for 3 seconds to enter the setup menu.
Press
Down
three times to reach the lockout password,
.
Press
Set/Ent
to enter the lockout password (the default is 0).
Press
Down
two times to access
(Output Group).
Press
Set/Ent
two times to access parameter
.
Press
Up
to select
(Retransmit).
Press
Set/Ent
to accept selection.
Press
Set/Ent
multiple times until
is selected.
Press
Down
two times to access
(Retransmit Group).
Press
Set/Ent
to access parameter
(Retransmit type).
Press
Down
to select
(Loop Power Supply).
Press
Set/Ent
to accept.
Press and hold
Set/Ent
for 3 seconds to exit the setup menu.
The Nova VirtualMeter assumes a 22°C or 72°F ambient temperature while programmed for a temperature input.