Virtual Meter Instructions

Main Menus

Program Analog Outputs
  1. Set Up as 15 VDC Voltage Pulse PID Control
    1. Press and hold Set/Ent for 3 seconds to enter the setup menu.
    2. Press Down three times to reach the lockout password,.
    3. Press Set/Ent to enter the lockout password (the default is 0).
    4. Press Down two times to access(Output Group).
    5. Press Set/Ent two times to access parameter.
    6. Verify the default setting of(PID Control). Change if required.
    7. Press Set/Ent to access parameter.
    8. Verify the default setting of(Solid State Relay VDC Pulse). Change if required.
    9. Press Set/Ent to accept if changed.
    10. Press Set/Ent multiple times until parameter(Cycle Time) is displayed.
    11. Press Up or Down to set the number of seconds for each time-proportional cycle of the voltage pulse.
    12. Press Set/Ent to accept the cycle time if changed.
    13. Press and hold Set/Ent for 3 seconds to exit the setup menu.
  2. Set Up as 4-20 mA PID Control
  3. Set Up as a Retransmitting Output
  4. Set Up as a Loop Power Supply
The Nova VirtualMeter assumes a 22°C or 72°F ambient temperature while programmed for a temperature input.