What's New at Precision Digital News from Precision Digital Rate/Totalizers, Fluidwell, NOVA Rate/Totalizers, Fluidwell, NOVA Precision Digital Pricelists Precision Digital Services Precision Digital Support Services Instrumentation Design & Sales JobsContact Precision Digital CorporationView Precision Digital Videos
ProVu PD6200 and PD6300 FLOW RATE / TOTALIZERS FOR ANALOG & PULSE INPUTS
   
   


Totalizer Capabilities Outputs Applications Connections

Mounting Dimensions Specifications Ordering Information Documentation

FLOW RATE / TOTALIZERS FOR ANALOG & PULSE INPUTS


ProVuMODEL PD6200 ANALOG INPUT   ProVuMODEL PD6300 PULSE INPUT
provu model pd6200 analog input
approvals

provu logo
ProVu model PD6300 pulse input
  • 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
  • Isolated 24 VDC @ 200 mA Transmitter Power Supply
  • Open Channel Flow with Programmable Exponent
  • Square Root Extraction
  • 32-Point Linearization
  • Pulse, Open Collector, NPN, PNP, TTL, Switch
  • Contact, Sine Wave (Coil), Square Wave Inputs
  • 5, 10 or 24 VDC Flowmeter Power Supply
  • Gate Function for Rate Display of Slow Pulse Rates
  • K-Factor, Internal Scaling, or External Calibration
  • 4-20 mA Output Option Converts the Pulse Input toan Isolated 4-20 mA Output

COMMON METER FEATURES

  • NEMA 4X, IP65 Front
  • Universal 85-265 VAC or 12/24 VDC Input Power
  • Large Dual-Line 6-Digit Display, 0.60" & 0.46"
  • Programmable Displays & Function Keys
  • Sunlight Readable Display
  • 2 or 4 Relays + Isolated 4-20 mA Output Options
  • External 4-Relay & Digital I/O Expansion Modules
  • RS-232, RS-422/485 Serial Communication Options
  • -40 to 65°C Operating Temperature Range
COMMON RATE/TOTALIZER FEATURES

  • Display Rate & Total at the Same Time
  • Rate in Units per Second, Minute, Hour, or Day
  • Total, Grand Total or Non-Resettable Grand Total
  • Password Protection for Total Reset
  • 9-Digit Totalizer with Total Overflow Feature
  • Any Relay for Rate or Total
  • 4-20 mA Output for Rate or Total
  • Sampling Relay
  • Total Stored in Non-Volatile Memory

PERFECT FOR FLOW APPLICATIONS

The PD6200 and PD6300 ProVumeters are 1/8 DIN flow rate/totalizers specifically designed for displaying flow rate and total from flowmeters with analog or pulse outputs. These flow rate/totalizers are particularly well-suited for flow applications because they can display flow rate and flow total at the same time, provide power to drive the flowmeter, and display flow total, flow grand total, or non-resettable flow total on up to nine digits.



ProVu PD6200 and PD6300 Rate/Totalizers


FRONT PANEL DISPLAY

Display Flow Rate, Total or Grand Total
The main display can be programmed to display flow rate, total or grand total, and the secondary display can be programmed to display flow rate, total or grand total, engineering units, custom legends or can be turned off. Both displays could also display relay set points or max and min values.

In the graphic above, the main display is displaying flow rate (as indicated by the “R” to the right of the number) and the secondary display is displaying flow total (as indicated by the T under the number.) The following photographs show typical ways these flow rate/totalizers can be programmed:


front panel display

Totalizer Overflow Displays Total to 9 Digits

These flow rate/totalizers can display up to nine digits of total flow with the total overflow feature. In the diagrams below, the flow totalizer is displaying 532,831,470 by toggling between a display of “oF 532” and “831470”. Notice the (T with arrow ▲ symbol) is lit up indicating the display is in overflow mode.

Totalizer Overflow Displays Total to 9 Digits




Environmentally Tough
environmentally tough


Rugged
A unique front panel design makes the ProVunearly impenetrable in typical applications. Here, the ProVueasily survives a direct hit on the display from a heavy 2" solid stainless steel ball dropped from eight feet. PD6200 rugged


TOTALIZER CAPABILITIES

These ProVuflow rate/totalizers can be programmed for a wide variety of totalilzer applications. They can display total, grand total, or non-resettable grand total with a time base of seconds, minutes, hours or days. The user can program a totalizer conversion factor, a non-resettable grand total, password protection and several total reset methods.

Non-Resettable Grand Total

The user can set up the grand total to be non-resettable by entering a specific password. Once this is done, the grand total can never be reset.

Totalizer Conversion Factor

The user can enter a totalizer conversion factor that allows the meter to display total in different units than the rate. For instance, a customer could measure flow rate in gallons per minute and total in hundredths of acre-feet.

Password Protection

The total and grand total can be password protected so they can be reset only by authorized personnel.

Total Password Grand total Password


Front Panel Total Reset

The three front panel function keys can be programmed to reset the total and grand total. This makes it possible for the user to reset either the total or the grand total by pressing the appropriate function key. Of course, if the total or grand total is password protected, they will not reset when the function key is pressed.
PD6200 front panel total reset

Remote Total Reset

An I/O expansion module can be used to remotely reset the total or grand total. The reset switch is wired into the module and the module is connected to the M-Link RJ45 socket at the back of the flow rate/totalizer.

Total Alarms

The ProVu’s four internal and four external relays can be set up to alarm when the total reaches a user-defined set point. A variety of reset modes are available and the user can also program time delays and fail safe operation.

FIELD EXPANSION MODULES

Add functionality to the ProVuin the field with easy-to-install external expansion modules. Add RS-232 or
RS-422/485 communications, I/O modules (up to 2), or 4-relay expansion module. The menu items for these modules do not appear until the module is connected, simplifying the basic menu. Relay and digital I/O modules
are shown below with optional DIN rail mounting kit, P/N PDA1002.

PD6200 field expansion modules

I/O Expansion Module

Four digital inputs and four digital outputs are available per expansion module. The ProVumeter will accept two of these modules. External digital inputs can function similarly to the front panel function keys. They can be configured to trigger certain events (i.e. reset total or grand total, acknowledge/reset alarms, reset max and/or min values, disable/enable all output relays, and hold current relay states), and provide direct menu access point.
Digital outputs can be used to remotely monitor ProVu’s alarm relay output states, or the states of a variety of actions and functions executed by the meter.

Relay Expansion Module

An external module containing four 3 amp Form A (SPST) relays can be added to the ProVuat anytime. Removable
screw terminal blocks accept 12 to 22 AWG wire.
PD6200 Relay Expansion Module
PD6200 Communication Module Communications Module

Serial communications on the ProVucan be added anytime with external RS-232 or RS-422/485 communication adapters.

OUTPUTS

Relay Outputs
PD6200 Relay Outputs
The ProVuhas up to four 3 A Form C relays (SPDT), giving you more fail-safe options upon power loss. Relay action can also be configured for input loop break protection. Set ON and OFF delay times when needed. Up to eight front panel indicators show alarm and/or relay state. All relays can be configured for 0-100% deadband.

Relay Operation & Configuration

There are powerful relay functions that can be configured in the ProVumeter, including:

  • Automatic reset only (non-latching)
  • Automatic + manual reset at any time (non-latching)
  • Latching (manual reset only)
  • Latching with clear (manual reset only after alarm condition has cleared)
  • Sampling (activated for a user-specified time)
  • User selectable fail-safe operation
  • Relay action for loss (break) of 4-20 mA input signal
  • Time delay (on and off), independent for each relay
  • Manual control mode

Analog Output

The isolated analog retransmission signal can be configured to represent the rate, total, grand total, maximum (peak) value, minimum (valley) value, or the value for any of the eight relay set points. While the output is nominally 4-20 mA, the signal will accurately accommodate ranges from 1 to 23 mA.

Auto/Manual Control

Take control of any output with this feature. All relays can be forced ON or OFF, and the 4-20 mA output signal can be set to any value within its range. This is particularly useful for valve control applications.

Isolated Transmitter Power Supplies

A powerful 24 V @ 200 mA power supply is a standard feature on the ProVumeter. It can be configured for 5, 10, or 24 V (default) by means of a simple internal jumper (see manual). An additional power supply (24 V @ 40 mA) is standard with the 4-20 mA output option.


NEMA 4 & 4X FIELD ENCLOSURES

Plastic, stainless steel, and painted steel NEMA 4X enclosures for up to 10 ProVumeters.

NEMA 4 and 4x field enclosures NEMA 4 and 4x field enclosures
PDA2811 PDA2706
Click here for a list of enclosures available.


EASY PROGRAMMING AND SETUP

Dual-Line Display & 4 Buttons

The user friendly dual-line display and four programming buttons make the ProVueasy to set up and program. The four buttons keep the user in control of the programming process, and the second line provides a reminder or prompt for the current programming step.

PD6200 Easy programming and setup Easy Programming and setup display 1
Input 1 Display 1

The meter on the left is prompting the user to enter the desired input value, which in this case will be 4 mA. A key feature of the ProVuis that it is not necessary to actually apply this input so the meter can be scaled without a calibrator.

The meter on the right is prompting the user to enter the desired display value that corresponds to Input 1. The right arrow moves the active digit to the right and the up arrow increases the value of the digit.


I/O Module for Remote Programming

The I/O module can be used to program the ProVuremotely, in essence giving the user control of the four front panel push buttons. This feature is particularly useful if the meter is mounted inside an explosion-proof enclosure.



METER COPY

The Copy feature is used to copy (or clone) all the settings from one ProVuto other ProVumeters in about 20 seconds! The Copy function is a standard feature on all meters. It does not require a communications adapter, only an optional cable assembly, P/N PDA1200. See the ordering information for complete details.

PD6200 meter copy

Copying Meter Settings



APPLICATIONS

PD6200 applications



Open Channel Flow

The PD6200, in combination with an ultrasonic level transmitter, makes for an economical way to measure and display open channel flow rate and total in most weirs and flumes and take periodic samples. All the user needs to do is enter the exponent for the weir or flume into the PD6200 and the PD6200 automatically raises the input signal to that power. Sampling can be based on the total flow or the flow rate. For instance, to display open channel flow rate and total from a 3 inch Parshall flume and take a one pint sample every 100,000 gallons, the user would program the PD6200 as follows:

Function Desire Programming
Open Channel Flow 3" Parshall flume Set Programmable Exponent to 1.547
Flow Rate Millions of Gallons per Day (MGD) Set 4 mA = 0 & 20 mA = 3.508
Time base = Day
Total Millions of Gallons Set Totalizer Conversion Factor = 1
(password protect total reset)
Non-Resettable Grand Total Program meter so grand total can never be reset Set non-resettable grand total password
Display Display Flow Rate and Total at the same time Set main display for Grand Total and secondary display to toggle between rate and total
Sampling Take a 1 pint sample every 100,000 gallons Set up relay for sampling and to trip every 0.1 million gallons. Set up sampling time such that 1 pint is sampled


total relay sampling operation



Differential Pressure Flow


The PD6200 can display flow rate and total by extracting the square root from the 4-20 mA signal from a differential pressure transmitter. The user selectable low-flow cutoff feature gives a reading of zero when the flow rate drops below a user selectable value.

differential pressure flow
  • Display Flow Rate
  • User Selectable Low-Flow Cutoff
  • Only 2 Calibration Points Required




Convert Pulse to 4-20 mA with PD6300

The PD6300 accepts the pulse output from a flowmeter and with the appropriate option installed can convert the pulse to a 4-20 mA signal. The 4-20 mA signal can be programmed to correspond to either the flow rate or the total flow.

convert pulse to 4-20 mA with PD6300

  • Use K-Factor or Multi-Point Scaling
  • ProVuPowers the Flowmeter
  • Display Flow Rate & Total

CONNECTIONS

PD6200

PD6200 connections



PD6300

PD6300 connections

MOUNTING DIMENSIONS

Mounting Dimensions

Notes:
1. Panel cutout required: 1.772" x 3.622" (45mm x 92mm)
2. Panel thickness: 0.040 - 0.250" (1.0mm - 6.4mm)
3. Mounting brackets lock in place for easy mounting
4. Clearance: Allow 6" (152 mm) behind the panel

SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C

General

Display: Main display: 0.60" (15 mm) high, second display: 0.46" (12 mm) high. Both displays are 6 digits (-99999 to 999999), red LEDs with leading zero blanking
Display Intensity: Eight user selectable intensity levels
Overrange: Display flashes 999999
Underrange: Display flashes -99999
Front Panel: NEMA 4X, IP65
Programming Methods: Four front panel buttons, digital inputs, PC and multi-point linearization utility, or cloning using Copy function
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months
Max/Min Display: Max (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power to the meter is turned off
Password: Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals. Pass 1: Allows use of the F1–F3 function keys. Pass 2: Allows use of the F1–F3 function keys and changing the set/reset points. Pass 3: Restricts all programming and F1–F3 keys. Total: Prevents resetting the total manually. Gtotal: Prevents resetting the grand total manually
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC 20 W max, or jumper selectable 12/24 VDC ±10%, 15 W max.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 5% @ 200 mA max (standard), (12/24 VDC powered models rated @ 100 mA max). 5 or 10 VDC @ 50 mA max, selectable with internal jumper J4
Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply
Environmental: Operating temperature range: -40 to 65°C. Storage temperature range: -40 to 85°C. Relative humidity: 0 to 90% non-condensing
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black
Mounting: 1/8 DIN panel cutout required: 3.622" x 1.772"(92 mm x 45 mm). Two panel mounting bracket assemblies are provided
Tightening Torque: Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall Dimensions: 4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Weight: 9.5 oz (269 g)
UL File Number: UL & c-UL Listed. E160849; 508 Industrial Control Equipment
Warranty: 3 years parts & labor


PD6200 Analog Inputs

Inputs: Field selectable: 0-20, 4-20 mA, ±10 VDC (0-5, 1-5, 0-10 V)
Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span
Display Update Rate: 5/second (200 ms)
Temperature Drift: 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient
Math Function: Linear, square root, programmable exponent, or round horizontal tank volume calculation
Multi-Point Linearization: 2 to 32 points
Programmable Exponent: 1.0001 to 2.9999
Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd
Calibration Range: Input range: 4-20 mA, ±10 V. Minimum span: 0.15 mA or 0.10 V. An Error message will appear if input 1 and input 2 signals are too close together
Input Impedance: Voltage ranges: greater than 1 MΩ. Current ranges: 50 - 100 Ω (depending on resettable fuse impedance)
Input Overload: Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed
Noise filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span
Normal Mode Rejection: Greater than 60 dB at 50/60 Hz


PD6300 Rate Inputs

Inputs: Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 kΩ pull-up to 3.3 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7 kΩ pull-up to 3.3 V @ 40 Hz
Low Voltage Mag Pickup (Isolated): Sensitivity: 125 mVp-p; Hysteresis: 30 mV (Order with MOD0077 for 20 mVp-p sensitivity)
Minimum Input Frequency: 0.0101 Hz. Minimum frequency is dependent on high gate setting
Maximum Input Frequency: 30,000 Hz
Input Impedance: Pulse input: Greater than 300 kΩ @ 1 kHz. Open collector/switch input: 4.7 kΩ pull-up to 3.3 V
Accuracy: ±0.03% of calibrated span ±1 count
Temperature Drift: Rate display is not affected by changes in temperature
Multi-Point Linearization: 2 to 32 points
Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
Decimal Point: Up to five decimal places or none: d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Calibration: May be calibrated using K-factor, scale using internal calibration, or calibrate by applying an external calibration signal
K-Factor: Field programmable K-factor converts input pulses to rate in engineering units. May be programmed from 0.00001 to 999,999 pulses/unit
Calibration Range: Input 1 signal may be set anywhere in the range of the meter; input 2 signal may be set anywhere above or below input 1 setting. Minimum input span between any two inputs is 10 Hz. An Error message will appear if the input 1 and input 2 signals are too close together
Filter: Programmable contact de-bounce filter: 40 to 999 Hz maximum input frequency allowed with low speed filter
Time Base: Second, minute, hour, or day
Gate: Low gate: 0.1-99.9 seconds; High gate: 2.0-999.9 seconds


Rate/Totalizer

Display Assignment: The main (Big) and small (Little) displays may be assigned to rate, total, grand total, alternate R & T, units, and set point
Rate Display Indication: 0 to 999999, lead zero blanking. “R” LED illuminates while displaying rate
Total Display & Total Overflow: 0 to 999,999; automatic lead zero blanking. “T” LED is illuminated while displaying total or grand total. Up to 999,999,999 with total-overflow feature. “oF” is displayed to the left of total overflow and ▲ LED is illuminated
Alternating Display: Either display may be programmed to alternate between rate and total or rate and grand total every 10 seconds
Total Decimal Point: Up to five decimal places or none: d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd. Total decimal point is independent of rate decimal point
Totalizer: Calculates total based on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed
Totalizer Rollover: Totalizer rolls over when display exceeds 999,999,999. Relay status reflects display
Total Overflow Override: Program total reset for automatic with 0.1 second delay and set point 1 for 999,999
Totalizer Presets: Up to eight, user selectable under setup menu. Any set point can be assigned to total and may be programmed anywhere in the range of the meter for total alarm indication
Programmable Total Reset Delay: 0.1 to 999.9 seconds; applied to the first relay assigned to total or grand total. If the meter is programmed to reset total to zero automatically when the preset is reached, then a delay will occur before the total is reset
Total Reset: Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications
Total Reset Password: Total and grand total passwords may be entered to prevent resetting the total or grand total from the front panel.
Non-Resettable Total: The grand total can be programmed as a non-resettable total by entering the password “050873”
Caution: Once the Grand Total has been programmed as “non-resettable” the feature cannot be disabled


Relays

Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP @ 125/250 VAC for inductive loads
Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads
Deadband: 0-100% of span, user programmable
Relay Assignment: Relays may be assigned to rate, total, or grand total
High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off)
Relay Operation: automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), off (disable unused relays), and manual control mode
Relay Reset: User selectable via front panel buttons, digital inputs, or PC
1. Automatic reset only (non-latching), when input passes the reset point or total is reset to zero
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (latching)
Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset
Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay
Fail-Safe Operation: Programmable and independent for each relay. Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state
Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter


Isolated 4-20 mA Transmitter Output


Output Source: Rate, total, grand total, max, min, set points 1-8, or manual control mode
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated: 4.000 to 20.000 = 4-20 mA output
Analog Output Programming: 23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
Accuracy: ± 0.1% FS ± 0.004 mA
Temperature Drift: 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient Note: Analog output drift is separate from input drift
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 5% @ 40 mA maximum, may be used to power the 4-20 mA output or other devices. Present on both AC & DC powered units
External Loop Power Supply: 35 VDC maximum
Output Loop Resistance:

Power supply Minimum Maximum
24 VDC 10 Ω 700 Ω
35 VDC (external) 100 Ω 1200 Ω

Serial Communications

Meter Address: 1 - 247
Baud Rate: 300 - 19,200 bps
Transmit Time Delay: Programmable between 0 and 199 ms or transmitter always on for RS-422 communication
Data: 8 bit (1 start bit, 1 stop bit)
Parity: None
Turn Around Delay: Less than 2 ms (fixed)


Digital I/O Expansion Module

Channels: 4 digital inputs & 4 digital outputs per module
System: Up to 2 modules for a total of 8 inputs & 8 outputs
Digital Input Logic: High: 3 to 5 VDC Low: 0 to 1.25 VDC
Digital Output Logic: High: 4.75 to 5 VDC Low: 0 to 0.4 VDC
Source Current: 10 mA maximum
Sink Current: 1.5 mA minimum
+5 V Terminal: To be used as pull-up for digital inputs only
Example: Connect normally open pushbuttons across +5 V & DI1-4


4-Relay Expansion Module

Relays: Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP @ 125/250 VAC for inductive loads


ORDERING INFORMATION

Products
PD6200
Model Description Price
PD6200-6R0        ProVu Analog Input Dual-line Flow Rate/Totalizer; No Options; Powered from 85-265 VAC        $319.00
PD6200-6R2        ProVu Analog Input Dual-line Flow Rate/Totalizer; 2 Relays; Powered from 85-265 VAC        $359.00
PD6200-6R3        ProVu Analog Input Dual-line Flow Rate/Totalizer; 4-20 mA Output; Powered from 85-265 VAC        $379.00
PD6200-6R4        ProVu Analog Input Dual-line Flow Rate/Totalizer; 4 Relays; Powered from 85-265 VAC        $399.00
PD6200-6R5        ProVu Analog Input Dual-line Flow Rate/Totalizer; 2 Relays + 4-20 mA Output; Powered from 85-265 VAC        $419.00
PD6200-6R7        ProVu Analog Input Dual-line Flow Rate/Totalizer; 4 Relays + 4-20 mA Output ; Powered from 85-265 VAC        $459.00
PD6200-7R0        ProVu Analog Input Dual-line Flow Rate/Totalizer; No Options; Powered from 12-24 VDC        $379.00
PD6200-7R2        ProVu Analog Input Dual-line Flow Rate/Totalizer; 2 Relays; Powered from 12-24 VDC        $419.00
PD6200-7R3        ProVu Analog Input Dual-line Flow Rate/Totalizer; 4-20 mA Output; Powered from 12-24 VDC        $439.00
PD6200-7R4        ProVu Analog Input Dual-line Flow Rate/Totalizer; 4 Relays; Powered from 12-24 VDC        $459.00
PD6200-7R5        ProVu Analog Input Dual-line Flow Rate/Totalizer; 2 Relays + 4-20 mA Output; Powered from 12-24 VDC        $479.00
PD6200-7R7        ProVu Analog Input Dual-line Flow Rate/Totalizer; 4 Relays + 4-20 mA Output; Powered from 12-24 VDC        $519.00
 
PD6300
Model Description Price  
PD6300-6R0        ProVu Pulse Input Dual-line Flow Rate/Totalizer; No Options; Powered from 85-265 VAC        $319.00
PD6300-6R2        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 2 Relays; Powered from 85-265 VAC        $359.00
PD6300-6R3        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4-20 mA Output; Powered from 85-265 VAC        $379.00
PD6300-6R4        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4 Relays; Powered from 85-265 VAC        $399.00
PD6300-6R5        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 2 Relays + 4-20 mA Output; Powered from 85-265 VAC        $419.00
PD6300-6R7        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4 Relays + 4-20 mA Output ; Powered from 85-265 VAC        $459.00
PD6300-7R0        ProVu Pulse Input Dual-line Flow Rate/Totalizer; No Options; Powered from 12-24 VDC        $379.00
PD6300-7R2        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 2 Relays; Powered from 12-24 VDC        $419.00
PD6300-7R3        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4-20 mA Output; Powered from 12-24 VDC        $439.00
PD6300-7R4        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4 Relays; Powered from 12-24 VDC        $459.00
PD6300-7R5        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 2 Relays + 4-20 mA Output; Powered from 12-24 VDC        $479.00
PD6300-7R7        ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4 Relays + 4-20 mA Output; Powered from 12-24 VDC        $519.00
 

Enclosures

PDA2300 Enclosure Family Enclosure Selection Utility
Model Description Price  
PDA2407        Plastic NEMA 4X Enclosure for 1 Meter (Any Type)        $199.00
PDA2411        Plastic NEMA 4X Enclosure for 2 Meter (Any Type)        $274.00
PDA2414        Plastic NEMA 4X Enclosure for 1 Type D + 1 Type A, B, C or E Meter        $274.00
PDA2504        Plastic NEMA 4X Enclosure for 4 Type A, B, C, or E Meters        $334.00
PDA2505        Plastic NEMA 4X Enclosure for 5 Type A, B, C, or E Meters        $354.00
PDA2506        Plastic NEMA 4X Enclosure for 6 Type A, B, C, or E Meters        $374.00
PDA2507        Plastic NEMA 4X Enclosure for 7 Type A, B, C, or E Meters        $474.00
PDA2508        Plastic NEMA 4X Enclosure for 8 Type A, B, C, or E Meters        $514.00
PDA2509        Plastic NEMA 4X Enclosure for 9 Type A, B, C, or E Meters        $554.00
PDA2510        Plastic NEMA 4X Enclosure for 10 Type A, B, C, or E Meters        $584.00
PDA2512        Plastic NEMA 4X Enclosure for 2 Type A, B, C, or E Meters        $359.00
PDA2522        Plastic NEMA 4X Enclosure for 1 Type D + 1 Type C Meter        $344.00
PDA2604        Stainless Steel NEMA 4X Enclosure for 4 Type A,B, C or E Meters        $734.00
PDA2605        Stainless Steel NEMA 4X Enclosure for 5 Type A,B, C or E Meters        $784.00
PDA2606        Stainless Steel NEMA 4X Enclosure for 6 Type A,B, C or E Meters        $839.00
PDA2622        Stainless Steel NEMA 4X Enclosure for 1 Type D + 1 Type C Meter        $499.00
PDA2704        Steel NEMA 4 Enclosure for 4 Type A, B, C, or E Meters        $419.00
PDA2705        Steel NEMA 4 Enclosure for 4 Type A, B, C or E Meters        $474.00
PDA2706        Steel NEMA 4 Enclosure for 5 Type A, B, C or E Meters        $524.00
PDA2722        Steel NEMA 4X Enclosure for 1 Type D + 1 Type C Meter        $329.00
PDA2811        Low-Cost Plastic NEMA 4X Enclosure for 1 Meter (Type A, B, C or E)        $114.00
PDA2812        Low-Cost Plastic NEMA 4X Enclosure for 2 Meters (Any type)        $159.00
PDA2821        Low-Cost Plastic NEMA 4X Enclosure for 1 Type D Meter + 1 Type A, B, C or E Meter        $179.00
  
Accessories
Model Description Price  
 PDA1002        ProVu DIN Rail Mounting Kit for Two Modules        $10.00
 PDA1004        ProVu 4 Relays Expansion Module        $80.00
 PDA1044        ProVu 4 Digital Inputs & 4 Outputs Module        $35.00
 PDA1200        ProVu Meter Copy Cable, 3' (0.9 m)        $10.00
 PDA1232        ProVu RS-232 Serial Adapter        $79.00
 PDA1485        ProVu RS-422/485 Serial Adapter        $79.00
 PDA7485-I        RS-232 to RS-422/485 Isolated Converter        $169.00
 PDA7485-N        RS-232 to RS-422/485 Non-Isolated Converter        $139.00
 PDA8232-N        USB to RS-232 Converter        $49.00
 PDA8485-I        USB to RS-422/485 Isolated Converter        $189.00
 PDA8485-N        USB to RS-422/485 Non-Isolated Converter        $159.00
 PDA9485-01        Ethernet Serial Server        $389.00
 PDX6901        Suppressor (snubber): 0.01µF/470Ω,        $10.00




DOCUMENTATION
PD6300: Instruction Manual
PD6200: Instruction Manual
PD6200-PD6300: Data Sheet
ProVu Accessories
Free Linearization PC Utility
Two Lines = More Information and Easier Setup + Easier Setup
Dual Line Display ProVu Pearl
Request a Sales Demonstration

See How You can Use Precision Digital Products for