SPECIFICATIONS
Except where noted all specifications
apply to operation at +25°C.
General
Input/Output: Modbus RTU RS-485
Display: 0.56" (14.2 mm) red LED, 6 digits;
displays from -199999 to 999999, automatic leading zero
blanking
Display Intensity: Eight user selectable intensity
levels
Decimal Point: Up to five decimal places: d.ddddd,
dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd
Front Panel: NEMA 4X, IP65; panel gasket provided
Programming Methods: Four front panel buttons
or via Modbus registers (Slave mode only)
Scaling: Input may be scaled from -199,999 to
999,999
Function: Linear, square root, or programmable
exponent from 0.50000 to 2.99999
Multi-Point Linearization: 2 to 16 points
Noise Filter: Programmable 2 to 199 (0 will disable
filter)
Bypass: 0.2 to 99.9% of full-scale
Cutoff: 0 to 999999; 0 disables cutoff
Display Update Rate: Master: 10/sec to 1 every
25.5 seconds;
Slave: Dependent on master device (PLC, DCS,
etc)
Overrange: Display flashes 999999
Underrange: Display flashes -199999
Max/Min Display: Stored until reset by user or
meter is turned off; user can reset by front panel buttons
or via Modbus registers.
Password: Restricts modification of programmed
settings.
Non-Volatile Memory: Settings stored for a minimum
of 10 years.
Power Options: 85-265 VAC, 50/60 Hz; 90-265 VDC,
20 W max or 12-36 VDC; 12-24 VAC, 6 W max.
Required Fuse: UL Recognized, 5 A max, slow-blow;
up to 6 meters may share one fuse.
Normal Mode Rejection: 64 dB at 50/60 Hz
Transmitter Supply: Isolated 24 VDC ±10%
@ 200 mA max
Isolation: 4 kV input/output-to-power line, 500
V input-to-output or
Operating Temperature: 0 to 65°C
Storage Temperature: -40 to 85°C
Relative Humidity: 0 to 90% non-condensing
Connections: Removable screw terminals accept
12 to 26 AWG
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0,
color: gray
Weight: 9.7 oz (275 g) (including options)
UL File Number: E160849; 508 Industrial Control
Equipment
Warranty: 3 years parts & labor
Extended Warranty: 1 or 2 years, refer to Price
List for details.
Master: Processes data read from a Modbus RTU
slave device (only one parameter at a time can be programmed
for reading).
Slave: Processes data sent from a Modbus RTU
master device.
Note that the relays and
the 4-20 mA output are functional in either mode.
Master Mode
Settings
Function Code: Select which Modbus function code
(03 or 04) to use
Register Number: 1 to 65536. Specifies which
register(s) to read in the slave device. Register number
is preceded by register type (3xxxxx or 4xxxxx). Five
or six digit register number allowed.
Data Type: Select the data format that the slave
device uses; select between Short (2 byte) and Long
(4 byte), Integers or Floating point (4 byte), Signed
or Unsigned (integer only), and byte order (big-endian
vs little-endian).
Slave Response Timeout: 0 to 25.5 seconds, limited
by Poll Time value. This is the time allowed for slave
to respond to a command.
Poll Time: 0.1 to 25.5 seconds between read commands.
Relays
Rating: 2 Form A (SPST) standard; 2 Form C (SPDT)
optional; rated 3 A @ 30 VDC or 3 A @ 250 VAC, resistive
loads
High or Low Alarm: User may program any alarm
for high or low
Deadband: 0-100% FS, user selectable
Relay Operation:
1. Automatic (non-latching)
2. Latching
3. Pump alternation control (up to
4 relays)
Relay Reset: Selectable via front panel or Modbus
registers
1. Automatic reset only (non-latching)
2. Automatic plus manual reset at
any time (non-latching)
3. Manual reset only, at any time
(latching)
4. Manual reset only after alarm condition
has cleared (latching)
Automatic Reset: Relays reset when input passes
the reset point
Manual Reset: Front panel button, Modbus registers
(Slave only)
Time Delay: 0 to 199 seconds, on and off delays,
programmable and independent for each relay
Fail-Safe Operation: Programmable, independent
for each relay
Communications Break: No change, Relay on, or
Relay off. Controls the condition the relay goes to
when a slave device does not reply (Master mode only).
Auto Initialization: When power is applied to
the meter, relays will reflect the state of the input
to the meter.
Serial Communications
Compatibility: EIA-485
Protocol: Modbus RTU
Address: 1 to 247. Specifies the address of the
slave device (Master mode) or the address of the PD865
(Slave mode).
Baud Rate: 300 to 19,200 bps
Data: 8 bits (1 start bit, 1 stop bit; 1 or 2
stop bits with no parity)
Parity: None, even, or odd
Byte-to-Byte Timeout: 0.01 to 2.54 seconds
Turn Around Delay: Less than 2 ms (fixed)
Isolated 4-20
mA Transmitter Output
Scaling Range: 1.000 to 23.000 mA; reverse scaling
allowed.
Calibration: Factory calibrated 4.000 to 20.000
mA
Accuracy: ±0.1% FS ±0.004 mA
Recalibration: Recommended at least every 12
months.
Temperature Drift: 50 PPM/°C
Transmitter Supply: Isolated 24 VDC ±10%
@ 200 mA max
Isolation: 500 V input-to-output or output-to-24
VDC supply; 4 kV output-to-power line
External Loop Power Supply: 35 VDC maximum
Output Loop Resistance:
|
Loop Resistance |
| Power Supply |
Minimum |
Maximum |
| 24 VDC |
10 Ω |
700 Ω |
| 35 VDC (external) |
100 Ω |
1200 Ω |
Data Source: Display value, maximum display value,
minimum display value, or Modbus register
Overrange: Programmable mA output for overrange
condition
Underrange: Programmable mA output for underrange
condition
Communications Break: Programmable
mA output when a slave device does not reply within the
Slave Response Timeout
Maximum Output: Programmable absolute maximum
mA output
Minimum Output: Programmable
absolute minimum mA output