PD8-154
PD8-158
Canadian Standards Association Atmosphères ExplosiblesEuropean ConformityIECEx Approval

Features

  • Fully Approved Explosion-Proof Annunciators
  • Switch, Open Collector NPN Transistor, and Logic Level Inputs
  • 4- or 8-Point Monitoring
  • 8 Field Selectable ISA Sequences Including First-Out
  • Multiple-Unit First-Out Indication
  • Free Custom Message Labels
  • Silence, Acknowledge, and Reset Functions
  • Sunlight Readable Indication
  • SafeTouch Through-Glass Button Programming
  • Annunciator Mountable at 0°, 90°, 180°, & 270°
  • 24 VDC @ 200 mA Power Available to Drive Other Devices (AC Models)
  • 2 SPDT Relays for Alarm Activated Devices
  • Operating Temperature Range: -55 to 65°C (-67 to 149°F)
  • CSA Certified as Explosion-Proof / Dust-Ignition-Proof / Flame-Proof
  • ATEX and IECEx Certified as Dust-Ignition-Proof / Flame-Proof
  • Input Power Options Include 85-265 VAC or 12-36 VDC
  • Built-in internal Audible Alarm with Silence Pushbutton
  • Flanges for Wall or Pipe Mounting
  • Explosion-Proof Aluminum or Stainless Steel NEMA 4X / IP68 Enclosures
  • Four 3/4" NPT Threaded Conduit Openings
  • Pipe Mounting Kits
  • Stainless Steel Tag Available
  • 3-Year Warranty

Overview

Front

PD8-154 Front

Connections

PD8-154 Connections

Introduction

The ProtEX-MAX PD8-150 series offers easy-to-use explosion-proof annunciators that can be set up to respond to alarm conditions based on 8 field selectable alarm sequences, including first-out indication. With either 4 or 8 switch inputs, the alarm channels accept normally open, normally closed, NPN open collector transistor, and logic level inputs. The annunciator is housed in a field-mountable, NEMA 4X/IP68 rated enclosure available in either aluminum or stainless steel for convenient indoor and outdoor installation.

Three front panel pushbuttons are used during sequence operation to silence the audible alarm, acknowledge the first out alarm, and reset cleared channels as required by the sequences. These functions can also be operated from hazardous-area remote devices using the remote control signal connectors, or in hazardous areas using the SafeTouch through-glass buttons.

The ProtEX-MAX PD8-150 series has two SPDT relays that can be used for additional external alarm indication, additional audible devices, or for process control.

To enhance the look of your ProtEX-MAX Annunciator, we strongly recommend you order Free custom message labels. These can be ordered at any time, just by filling out a convenient on-line form at Free Custom Message Labels.

General

Display: PD8-154: Four red LED channel indicators. PD8-158: Eight red LED channel indicators. One green LED power indicator.
Alarm Messages: Custom printed adhesive clear labels.
Area: PD154, 1.25" x .60" (32 mm x 15 mm), 4 messages PD158, 1.25" x .25" (32 mm x 6 mm), 8 messages
User specified size and length, up to 4 lines (PD154) or 2 lines (PD158) of 14 characters of size 9 pt fonts.
Programming Methods: Rear 4-position switch for sequence selection and horn operation. Three SafeTouch through-glass buttons for NO/NC input selection, sequence option, and operation when cover is installed. Three internal pushbuttons when cover is removed.
Audible Alarm: 85 dB internal horn. The use of an external explosion-proof horn is recommended due to the internal horn's audibility being dampened by the explosion-proof enclosure.
Noise Filter: 40 ms debounce on inputs and external push buttons.
Shared First-Out Systems: 1 ms unit-to-unit delay. Maximum of 200 units in the shared first-out system.
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Power Options: 85-265 VAC, 50/60 Hz; 90-265 VDC, 20 W max; or 12-36 VDC, 12-24 VAC, 6 W max.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow. Up to 6 annunciators may share one 5 A fuse
Isolated Power Supply: 24 VDC ± 10% @ 200 mA max Standard on 85-265 VAC powered units only.
Isolation: 4 kV input/output-to-power line.
Overvoltage Category: Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Environmental:
T6 Class operating temperature range: Ta = -40 to 60°C
T5 Class operating temperature range: Ta = -40 to 65°C
Storage temperature range: -55 to 85°C (-67 to 185°F)
Relative humidity: 0 to 90% non-condensing
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire.
Mounting: Four slotted flanges for wall mounting or NPS 1½" to 2½" or DN 40 to 65 mm pipe mounting.
Overall Dimensions: 6.42" x 7.97" x 8.47" (W x H x D) (163 mm x 202 mm x 215 mm)
Weight: Aluminum: 14.7 lbs (6.67 kg); Stainless Steel: 23.5 lbs (10.66 kg)
Warranty: 3 years parts & labor

Inputs

Input Types: NO or NC switches: No external excitation required.
Open collector transistor: Open circuit voltage approx. 3.3 VDC.
Logic Levels: LOW = 0 to 0.9 VDC, HIGH = 2.4 to 28 VDC
Update Rate: 41 ms following alarm state; 1 ms for alarm state clear.
Sequences: Input follower, ISA Sequences A, F1A, F2A, F3A, M, F1M, and F3M per ISA Standard ISA-18.1-1979 R2004.
Sequence Options: A, F1A, F2A, F3A, M, F1M, F2M, and input follower with selectable options -1 (silence push button), -4 (no lock-in), and -6 (no horn) per ISA Standard ISA-18.1-1979 R2004

Relays

Rating: 2 SPDT (Form C); rated 3 A @ 30 VDC or 3A @ 250 VAC resistive load; 1/14 HP @ 125/250 VAC for inductive loads.
Electrical Noise Suppression: A suppressor (snubber) should be connected to each relay contact switching inductive loads to prevent disruption to the microprocessor's operation. Recommended suppressor value: 0.01 µF/470 Ω, 250 VAC (PDX6901).
Relay Operation: Relay 1: Alarm state until alarm is acknowledged. Relay 2: Alarm state if any channel indicating alarm condition.
Fail-Safe Operation: Programmable independent for each relay.
Note: In fail-safe mode, relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.


Enclosure

Material-AL Models: ASTM A413 LM6 die-cast aluminum, copper-free, enamel coated
-SS Models: ASTM A743 CF8M investment-cast 316 stainless steel
GasketFluoroelastomer
RatingNEMA 4X, IP68 Explosion-proof
Color-AL: Blue
-SS: Silver
WindowBorosilicate glass
ConduitsFour ¾" NPT threaded conduit openings
Conduit Stopping PlugsSold separately
FlangesTwo built-in flanges for wall and pipe mounting.
Tamper-Proof SealCover may be secured with tamper-proof seal.
Overall Dimensions6.42" x 7.97" x 8.47" (W x H x D)
(163 mm x 202 mm x 215 mm)
WeightAL: 14.7 lbs (6.67 kg)
SS: 23.5 lbs (10.66 kg)
ATEXFlameproof
ATEXII 2GD
Ex db IIC Gb
Ex tb IIIC Db
IP66/IP68
Tamb: -55°C to +85°C
Certificate No.: Sira 19ATEX1252U
IECExFlameproof and dust protection
Ex db IIC Gb
Ex tb IIIC Db
IP66/IP68
Tamb: -55°C to +85°C
Certificate No.: IECEx SIR 19.0075U
CSAClass I, Division 1, Groups A, B, C, D
Class II, Division 1, Group E, F, G
Class III
Ex db IIC Gb
Ex tb IIIC Db
Class I, Zone 1, AEx db IIC Gb
Zone 21, AEx tb IIIC Db
IP66/IP68/TYPE 4X
Tamb: -55°C to +85°C
Certificate No.: 80011200
ULClass I, Division 1, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class III
Class I, Zone 1, AEx db IIC Gb
Zone 21, AEx tb IIIC
Ex db IIC Gb
Ex tb IIIC Db
IP66/IP68/TYPE 4X
Tamb: -55°C to +85°C
Certificate Number: E518920
Note: The above approvals are for the enclosure only. See below for approvals on the entire instrument.


General Compliance Information

Electromagnetic Compatibility

EmissionsEN 55022
Class A ITE emissions requirements
Radiated EmissionsClass A
AC Mains Conducted EmissionsClass A
ImmunityEN 61326-1
Measurement, control, and laboratory equipment
EN 61000-6-2
EMC heavy industrial generic immunity standard
RFI - Amplitude Modulated80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast Transients±2kV AC mains, ±1kV other
Electrostatic Discharge±4kV contact, ±8kV air
RFI - Conducted10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge±2kV Common, ±1kV Differential
Surge1KV (CM)
Power-Frequency Magnetic Field30 A/m 70%V for 0.5 period
Voltage Dips40%V for 5 & 50 periods
70%V for 25 periods
Voltage Interruptions<5%V for 250 periods
Note: Testing was conducted on meters with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.


Product Ratings and Approvals

CSAClass I, Division 1, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1
Class I Zone 1 Ex db IIC
Zone 21 Ex tb IIIC T90°C
-55°C < Tamb. < +60° C; Temperature Code T6
-55°C < Tamb. < +65° C; Temperature Code T5
Enclosure Type 4X & IP66 / IP68
Certificate Number: 2531731
ATEXII 2 G D
Ex db IIC T* Gb
Ex tb IIIC T90°C Db IP68
Ta = -55°C to +*°C
*T6 = -55°C to +60°C
*T5 = -55°C to +65°C
Certificate Number: Sira 12ATEX1182X
IECExEx db IIC T* Gb
Ex tb IIIC T90°C Db IP68
Ta = -55°C to +*°C
*T6 = -55°C to +60°C
*T5 = -55°C to +65°C
*T5 = -55°C to +65°C
Certificate Number: IECEx SIR 12.0073X
ATEX/IECEx Specific Conditions of Use:
  1. The equipment label and epoxy coating may generate an ignition-capable level of electrostatic charges under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charges on non-conducting surfaces. Additionally, cleaning of the equipment should be done only with a damp cloth.
  2. Flameproof joints are not intended to be repaired.
  3. All entry closure devices shall be suitably certified as “Ex d”, “Ex t” and “IP66/68” as applicable. Suitable thread sealing compound (non-setting, non-insulating, non-corrosive, not solvent based, suitable for the ambient rating) must be used at the NPT conduit entries to achieve the IPx8 rating while maintaining the Ex protection concept.
Year of Construction

This information is contained within the serial number with the first four digits representing the year and month in the YYMM format.

For European Community:

The ProtEX-MAX must be installed in accordance with the ATEX directive 2014/34/EU, and the product certificate Sira 12ATEX1182X.

Order Free Message Labels for this Product

PD138/PD158 Label Text
Please provide the text you would like to appear on the message label. 2 lines per message, 14 characters max per line.
Message 1
Message 2
Message 3
Message 4
Message 5
Message 6
Message 7
Message 8
PD154 Label Text
Please provide the text you would like to appear on the message label. 4 lines per message, 14 characters max per line.
Message 1
Message 2
Message 3
Message 4

Applications


Level Monitoring with Level Switches

The PD8-154 ProtEX-MAX 4-Point Annuciator is ideal for tank level switch monitoring.
  • Up to 8 Individually Labeled Level Switch Inputs
  • 24 VDC Level Switch Power Supply
  • Relays for External Horns and Light Alarms
  • Easy NEMA 4X Mounting Enclosures
  • Sunlight Readable Indication



Temp Monitoring with PD8-765 and PD8-7000 Explosion-Proof Meters

Connect the PD8-765 and PD8-7000 ProtEX-MAX alarm relays to the PD8-154 ProtEX-MAX 4-Point Annuciator for temperature alarm monitoring.
  • First-Out Indication for Heating/Cooling Systems
  • Multiple Unit First-Out Indication
  • Remote Silence, Acknowledge, and Reset
  • Internal Audible Horn
  • Fail-Safe Relays for Critical Applications

Connections


loader.gif