PD6262 & PD6363 ProVu Dual-Input Flow Rate / Totalizers

PD6262 and PD6363

ProVu PD6262 ANALOG INPUT

ProVu PD6363 PULSE INPUT

Inquire About This Product ProVu Series Details ProVu Series Videos
Totalizer Capabilities Outputs Applications Connections
Mounting Dimensions Specifications Ordering Information Documentation


COMMON METER FEATURES

•  Rate, Total, and Grand Total for Each Input    Channel
•  Addition, Difference, Average, Multiplication,    Division, Min, Max, Weighted Average, Ratio,    Concentration, & More
•  NEMA 4X, IP65 Front
•  Available with Universal 85-265 VAC or 12/24    VDC Input Power
•  Large Dual-Line 6-Digit Display, 0.60" & 0.46"
•  Sunlight Readable Display Models
•  2 or 4 Relays + Isolated 4-20 mA Output Options
•  External 4-Relay, Dual Analog Output, and Digital    I/O Expansion Modules
•  USB, RS-232, & RS-485 Serial Communications
   Expansion Modules
•  On-Board Digital Input
•  Modbus RTU Communication Protocol Standard
•  Isolated 24 VDC Transmitter Power Supply
•  Configure, Monitor, and Datalog from a PC with
   Free MeterView Pro Software





ProVu PD6262 and PD6363 Dual-Input Rate/Totalizers

PD6262 DUAL-INPUT ANALOG RATE/TOTALIZER

•  Analog Dual-Inputs with Math Functions
•  0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs

PD6363 DUAL-INPUT PULSE
RATE/TOTALIZER


•  Pulse, Open Collector, NPN, PNP, TTL, Switch Contact,
   Sine Wave (Coil), Square Wave Inputs
•  Gate Function for Display of Slow Pulse Rates

PERFECT FOR FLOW APPLICATIONS

The PD6262 and PD6363 ProVu meters are multipurpose, easy to use digital dual analog/pulse input flow rate/totalizers specifically designed for displaying flow rate and total from flowmeters with analog or pulse outputs. The displays, relays, and the analog/pulse outputs may be assigned to the rate, total, or grand total of input channels A or B; or math result channel C. Three of the front panel buttons can be custom-programmed for a specific operation.

KEY FEATURES

Dual-Input Process Meter

The PD6262 has two process input channels (A & B) capable of accepting current (0-20, 4-20 mA) and voltage (±10, 0-5, 1-5, 0-10 VDC). The PD6363 accepts two pulse (e.g. ±40 mV to ±8 V), square wave (0-5 V, 0-12 V, or 0-24 V), open collector, NPN, PNP, TTL or switch contact signals. Each input is programmed separately, with independent input type selection and scaling. These inputs may be displayed individually as part of the customizable dual-line display, or used with a wide range of math functions.

Analog (PD6262)

Totalizer Overflow Displays Total to 9 Digits

Pulse (PD6363)

Totalizer Overflow Displays Total to 9 Digits

Powerful Math Functions

The PD6262/PD6363 uses two rate input channels (A & B) with total and grand total for each in a variety of powerful math functions designed for a wide range of flow applications. Programmable adder (P) and factor (F) constants allow each formula to be customized as needed for a specific application. The math function (C) may be displayed with units, tags, channel A or B, rate, total or grand total, and in other useful combinations.

Name Function Setting
Addition (A+B+P)*F Sum
Difference (A-B+P)*F diF
Absolute diff. ((Abs(A-B))+P)*F
Average
(((A+B)/2)+P)*F
Multiplication ((A*B)+P)*F
Divide ((A/B)+P)*F
Max of A or B ((AB-Hi)+P)*F
Min of A or B ((AB-Lo)+P)*F
Draw ((A/B)-1)*F
Weighted Avg. ((B-A)*F)+A
Ratio (A/B)*F
Concentration (A/(A+B))*F
Total Addition (tA+tB+P)*F
G. Tot. Addition (GtA+GtB+P)*F
Total Difference (tA-tB+P)*F
G. Tot. Difference (GtA-GtB+P)*F
Total Ratio (tA/tB)*F
Total Percent (tA/(tA+tB))*100

Note: t = total, Gt = grand total. The F constant can be any value from 0.00001 to 999999. If the value is less than 1, it will have the same effect as a divider. For example, the average could also be derived by using (A+B)*F, where F = 0.500.

Customizable Displays

The ProVu has two red LED displays, an Upper display 0.60" (15 mm) high, and a Lower display 0.46" (12 mm) high. Each display is a full 6 digits (-99999 to 999999). The displays can be set up to read input channels (A or B), rate, total, or grand total, math function channel C, toggle between A & B, B & C, A & C, A & B & C, toggle between channels A, B, or C & units, the max/min of any of the channels, including the math channel (C), set points, or the Modbus input. This allows the display to be setup to display whatever variables are most valuable to the application. Here are just a few examples.

Math Function & Tag
The Upper display shows the math function result (C). The Lower display shows a custom label, in this case the math function used.
Math Function & Totals A & B
The Upper display shows the math function result (C). The Lower display alternates between totals A and B, with an indicator for each when being displayed.
Input Channels A & B Total
Both input channels are displayed, input A total on the Upper display and input B total on the Lower display. Indicators show A or B to label the display channel.

Totalizer Overflow Displays Total to 9 Digits

These flow rate/totalizers can display up to nine digits of total flow with the total overflow feature. In the diagrams below, the flow totalizer is displaying 532,831,470 by toggling between a display of "oF 532" and "831470". Notice the "oF" stands for overflow.

Totalizer Overflow Displays Total to 9 Digits

Simplified & Dynamic Menu System

The ProVu minimizes the menu selections by auto-detecting the installed options to determine what menu navigation is required. For example, extra menu items for the relay expansion module, I/O expansion, etc. are not present unless those options have been installed.

PD6200 rugged

Rugged

A unique front panel design makes the ProVu digital panel meter nearly impenetrable in typical applications. Here, the ProVu easily survives a direct hit on the display from a heavy 2" solid stainless steel ball dropped from eight feet.




Optional SunBright Display Models

ProVu's SunBright display models have an extra bright LED display. They are perfect for applications where visibility may be impaired by direct sunlight, smoke, fog, dust, or distance. Option is available on all ProVu models.

Alternating Display

Certain display options alternate the display information. A single display can show input variable information as well as that channel's unit or tag. Input and math function channels, gross and net values, and select inputs and the math result may also alternate on a single display. Below are just a few of the options for setting up a single display to alternate information.
Alternating input channels and total and units

Environmentally Protected

The ProVu has standard UV protection, a NEMA 4X front panel, extremely durable face plate, performs in a wide ambient operating temperatures, and is CE Certified (high noise and RF immunity).

DIGITAL COMMUNICATIONS

Modbus® RTU Serial Communications

With the purchase of a serial communication adapter, ProVu meters can communicate with any Modbus Master device using the everpopular Modbus communications protocol that is included in every ProVu. This greatly increases the flexibility of the meter.

Meter Copy

The Copy feature is used to copy (or clone) all the settings from one ProVu to other ProVu meters in about 20 seconds! The Copy function is a standard feature on all meters. It does not require a communications adapter, only an optional cable assembly, P/N PDA1200. See the ordering information for complete details.
PD6200 meter copy


METERVIEW® PRO SOFTWARE

Watch the MeterView Pro serial comm video ProVu series meter using the PC-based MeterView Pro (MVP) software (serial communications adapter required). MVP makes complete meter configuration simple and fast. Copying one meter configuration to another, as well as saving or retrieving a meter configuration file is a snap. MVP's linearization utility makes even a 32-point linearization task clear and easy to do. We also included a basic meter monitor and data logger for use with a ProVu. Of course, with ProVu's powerful Modbus protocol, custom programs can be made even more versatile. For more details on MeterView Pro, click here.

TOTALIZER CAPABILITIES

ProVu flow rate/totalizers can be programmed for a wide variety of totalizer applications. Each input channel has a total, grand total, or non-resettable grand total with a time base of seconds, minutes, hours or days. The user can program a totalizer conversion factor for each channel, a non-resettable grand total, password protection, and several total reset methods.

Non-Resettable Grand Total

The user can set up the grand total to be non-resettable by entering a specific password. Once this is done, the grand total can never be reset.

Totalizer Conversion Factor

The user can enter a totalizer conversion factor for each channel that allows the meter to display total in different units than the rate. For instance, a meter could display flow rate in gallons per minute and total in hundredths of acre-feet.Total and Grand Total Password

Totalizer Password Protection

The total and grand total can be password protected so they can be reset only by authorized personnel

Remote Total Reset

An I/O expansion module or F4 digital input can be used to remotely reset the totals or grand totals. The reset switch is wired into the module or F4 input and the module is connected to the M-Link RJ45 connector at the back of the flow rate/totalizer.

Total Alarms

The ProVu's four internal and four external relays can be set up to alarm when the total of channel A or B, or channel C math based on the totals, reaches a user-defined set point. A variety of reset modes are available and the user can also program time delays and fail-safe operation.

PD6200 front panel total reset

Front Panel Total Reset

The three front panel function keys can be programmed to reset the total and grand total. This makes it possible for the user to reset either the total or the grand total by pressing the appropriate function key. Of course, if the total or grand total is password protected, they will not reset when the function key is pressed.





PD6200 field expansion modules

FIELD EXPANSION MODULES

Add functionality to the ProVu in the field with easy-to-install external expansion modules. Add RS-232 or RS-485 communications, I/O modules (up to 2), and 4-relay expansion module. The menu items for these modules do not appear until the module is connected, simplifying the basic menu. Relay and digital I/O modules are shown to the right with optional DIN rail mounting kit, P/N PDA1002.

PDA1004 Relay Expansion Module

An external module containing four 3 A Form A (SPST) relays can be added to the ProVu at anytime. Removable screw terminal blocks accept 12 to 22 AWG wire.

PDA1011 Dual Analog Output Expansion Module

The PDA1011 is a dual analog output expansion module that is connected to the meter using a CAT5e cable provided with each module. For the ProVu to recognize installed PDA1011 analog outputs the module must be connected by the M-Link connector to the ProVu and each analog output to be used must be wired to and powered by a separate DC supply powering the ProVu.
Note: Works with dual-input meters only.

PDA1044 I/O Expansion Module

Four digital inputs and four digital outputs are available per expansion module. The ProVu meter will accept two of these modules. External digital inputs can function similarly to the front panel function keys or on-board digital input F4. They can be configured to trigger certain events (i.e. acknowledge/reset alarms, reset max and/or min values, disable/enable all output relays, and hold current relay states), provide direct menu access point, or mimic front panel keys. The I/O module can be used to configure the ProVu remotely, in essence giving the user control of the four front panel push buttons. This feature is particularly useful if the meter is mounted inside an explosion-proof enclosure.

Digital outputs can be used to remotely monitor ProVu's alarm relay output states, or the states of a variety of actions and functions executed by the meter.

PDA1232, PDA1485, & PDA8008 Communication Modules

Serial communications on the ProVu can be added anytime with external PDA1232 (RS-232), PDA1485 (RS-485), or PDA8008 (USB) communication adapters.

OUTPUTS

Analog Outputs

Each isolated analog retransmission signal can be configured to represent the channel A or B rate/process variable (PV), total, grand total, maximum (peak) value or minimum (valley) value; Channel C; math value; or the value for any of the eight relay set points, manual setting control, or Modbus input. While the output is nominally 4-20 mA, the signal will accurately accomodate under and over ranges from 1 to 23 mA.

Relay Outputs

The ProVu has up to four 3 A Form C relays (SPDT) with multiple power loss fail-safe options. Each relay may be assigned to input channel A or B, rate, total or grand total, or math result (C). Relays can be configured for proper protective action upon input loop break. Relay ON and OFF delay times are user adjustable. Up to eight front panel indicators show alarm and/or relay state. All relays can be configured for 0-100% deadband.

Relay Operation/Configuration

There are powerful relay functions that can be configured in the ProVu meter, including:
  • Automatic reset only (non-latching)
  • Automatic + manual reset at any time (non-latching)
  • Latching (manual reset only)
  • Latching with clear (manual reset only after alarm condition has cleared)
  • Pump alternation control (automatic reset only)
  • Sampling (activated for a user-specified time)
  • User selectable fail-safe operation
  • Relay action for loss (break) of 4-20 mA input signal
  • Time delay (on and off), independent for each relay
  • Manual control mode
  • Interlock relay mode

Auto/Manual Control

Manual Output Control

Take control of any output with this feature. All relays can be forced ON or OFF, and the 4-20 mA output signal can be set to any value within its range. When the relays and 4-20 mA output are controlled manually, an LED labeled "M" is turned on and the associated Alarm LEDs (1-8) flash every 10 seconds indicating that the meter is in manual control mode.

Sampling Function (PV Triggered Timed Relay)

The sampling function allows the operator to set a set point for a "sampling" relay. When the process (rate or total) reaches that set point, it will close that relay's contacts for a preset period of time (0.1 to 5999.9 seconds). An example of its use may be for wastewater sampling. When the wastewater total reaches a preset total interval (i.e. every 10,000 gallons), the relay contacts would close for a preset time, and by some means (light, horn, etc.) alert someone to take a sample, or provide the trigger to automatically take a sample of the wastewater. The utility of this function can, of course, be expanded beyond sampling and be used whenever a timed relay output closure is required when the rate or a total interval reaches a certain set point.
Interlock Relay

Interlock Relay(s)

This function allows a process to use one or more very low voltage input signals or simple switch contacts to control the state of one or more internal "interlock" relays. A violation (i.e. loss of input, open switch, or open circuit) forces one or more N/O interlock relay contacts to open. One input can be used in series with a number of interlock switches, or up to eight inputs can be required to force-on one (or more) internal interlock relays. Please see Application Note AN-1008 for more information. Requires PDA1044 Digital I/O module or use of on-board digital input F4.

APPLICATIONS

Differential Pressure Flow (PD6262)

The PD6262 can display flow rate and total by extracting the square root from the 4-20 mA signal from differential pressure transmitters. The user selectable low-flow cutoff feature gives a reading of zero when the flow rates drop below a user selectable value.
  • Display Flow Rate
  • User Selectable Low-Flow Cutoff
  • Only 2 Calibration Points Required

Open Channel Flow (PD6262)

PD6200 applications
The PD6262, in combination with ultrasonic level transmitters, makes for an economical way to measure and display open channel flow rates and totals in most weirs and flumes, and take periodic samples. All the user needs to do is enter the exponents for the weirs or flumes into the PD6262 and the PD6262 automatically raises the input signals to those powers. Sampling can be based on the total flow or the flow rate. Each channel's signal input conditioning is programmed independently.

Convert Pulse to 4-20 mA (PD6363)

Pulse to Current
The PD6363 accepts pulse outputs from flowmeters and with the appropriate option installed, can convert the pulses to a 4-20 mA signal. The 4-20 mA signal can be programmed to correspond to either the flow rate or the total flow.
  • Use K-Factor or Multi-Point Scaling
  • ProVu Powers the Flowmeter
  • Up to 3 Analog Outputs

NEMA 4 & 4X FIELD ENCLOSURES

Thermoplastic and stainless steel NEMA 4X, and painted steel NEMA 4 enclosures for up to 10 ProVu meters are available. Please visit our Enclosure Selection Utility at www.predig.com/esu for an easy way to find the right enclosure.
PDA2811 Low Cost Enclosure
PDA2811
Plastic Low-Cost Enclosure
PDA2302 Plastic Economical Enclosure
PDA2302
Plastic Economical
PDA2604 Stainless Steel Enclosure
PDA2604
Stainless Steel

CONNECTIONS

PD6262

PD6262 connections

PD6363

PD6363 connections

MOUNTING DIMENSIONS

Mounting Dimensions
Notes:
1. Panel cutout required: 1.772" x 3.622" (45mm x 92mm)
2. Panel thickness: 0.040 - 0.250" (1.0mm - 6.4mm)
3. Mounting brackets lock in place for easy mounting
4. Clearance: Allow 6" (152 mm) behind the panel

SPECIFICATIONS

Except where noted all specifications apply to operation at +25°C

General

Display: Upper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. 6 digits each (-99999 to 999999), red LEDs with lead zero blanking.
Display Intensity: Eight user selectable intensity levels
Display Update Rate: (PD6262): 5/second (200 ms) (PD6363): Rate: 10 per second; up to 1 per 100 seconds (and is a function of Low Gate setting); Total: 10 per second (fixed)
Overrange: Display flashes 999999
Underrange: Display flashes -99999
Display Assignment: The Upper and Lower displays may be assigned to show: One or more rate channels: Channel A (Ch-A), B (Ch-B), or C (Ch-C), Toggle between rate channels: Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C, Total or grand total: Ch-A or Ch-B, Rate and total or grand total: Ch-A, Ch-B, Relay set points, Max and/or min values: Ch-A, Ch-B, or Ch-C, Toggle between any rate channel & units, Toggle between any rate/math channel & units, Total and units: Ch-A or Ch-B, Toggle between totals: Ch-A & Ch-B; Ch-A, Ch-B, and sum of Ch-A and Ch-B, Modbus input. The lower display may also be set to show engineering units or be off, with no display.
Programming Methods: Four front panel buttons, digital inputs, PC and MeterView Pro software, Modbus registers, or cloning using Copy function.
Max/Min Display: Max/min readings reached by the process are stored until reset by the user or until power to the meter is cycled.
Password: Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals.
   Pass 1: Allows use of function keys and digital inputs
   Pass 2: Allows use of function keys, digital inputs and editing set/reset points
   Pass 3: Restricts all programming, function keys, and digital inputs.
   Total: Prevents resetting the total manually
   Gtotal: Prevents resetting the grand total manually
Noise Filter: (PD6262) Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: (PD6262) Programmable from 0.1 to 99.9% of calibrated span
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC 20 W max, or jumper selectable 12/24 VDC ±10%, 15 W max.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 10%. Selectable for 24, 10, or 5 VDC supply (internal jumper J4).
ProVu Series (PD6262/PD6363): 85-265 VAC models rated @ 200 mA max, 12/24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply. ProtEX-MAX (PD8 Series): All models transmitter supply rated @ 25mA max.
Normal Rejection Mode: (PD6262) Greater than 60 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
Overvoltage Category: Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Environmental: ProVu Series (PD6262/PD6363): Operating Temperature Range: -40 to 65°C, Storage Temperature Range: -40 to 85°C, Relative Humidity: 0 to 90% non-condensing
ProtEX-MAX (PD8 Series): T6 Class operating temperature range Ta = -40 to 60°C, T5 Class operating temperature range Ta = -40 to 65°C
See LIM8 ProtEX-MAX instruction manual for additional details.
Max Power Dissipation: ProtEX-MAX (PD8 Series): Maximum power dissipation limited to 15.1 W. See LIM8 ProtEX-MAX instruction manual for additional details.
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black
Mounting: 1/8 DIN panel cutout required: 3.622" x 1.772" (92 mm x 45 mm). Two panel mounting bracket assemblies are provided.
Tightening Torque: Screw terminal connectors: 5 lb-in (0.56 Nm)
Dimensions: 4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Weight: 9.5 oz (269 g)
Warranty: 3 years parts & labor

Dual Input Functionality

Analog Inputs: (PD6262) Two inputs, each separately field selectable: 0-20, 4-20 mA, ±10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)
Pulse Inputs: (PD6363) Two, Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 kΩ pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7Ω kpull-up to 5 V @ 40 Hz; Modbus PV (Slave) Channels: Channel A, Channel B, Channel C (Math channel)
Programmable Constants: Constant P (Adder): -99.999 to 999.999, default: 0.000, Constant F (Factor): 0.001 to 999.999, default: 1.000
Sequence of Operations for Input Programming:
   1.  Select Input for A and B
   2.  Set up the rate, total, and grand total engineering units for channels A & B, and units for math channel C
   3.  Set up rate, total, and grand total decimal points for channels A & B, and decimal point for math channel C
   4.  Program channel A & B rate parameters
   5.  Program channel A & B total and reset parameters
   6.  Set up the big and little displays and display intensity
   7.  Select the transfer function for A & B (e.g. Linear)
   8.  Select Math function for Channel C
   9.  Program constants for Factor (F) and Adder (P)
   10. Program cutoff values for A and B
Low Voltage Mag Pickup: (PD6363) Sensitivity: 40 mVp-p to 8Vp-p
Minimum Input Frequency: (PD6363) 0.001 Hz Minimum frequency is dependent on high gate setting.
Maximum Input Frequency: (PD6363) 30,000 Hz (10,000 for low voltage mag pickup)
Accuracy: (PD6262) ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span (PD6363) ±0.03% of calibrated span ±1 count
Temperature Drift: 0.005% of calibrated span/°,C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 07°C ambient
(PD6363) Rate display is not affected by changes in temperature.
Signal Input Conditioning: (PD6262) Linear, square root, programmable exponent.
Multi-Point Linearization: 2 to 32 points for channel A and B
Programmable Exponent: (PD6262) 1.0001 to 2.9999
Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd.
Calibration Range (PD6262):
Input Range Minimum Span
Range Input 1 & Input 2
4-20 mA 0.15 mA
±10 V 0.10 V
An Error message will appear if input 1 and input 2 signals are too close together.
Calibration Range (PD6363): Input 1 signal may be set anywhere in the range of the meter; input 2 signal may be set anywhere above or below input 1 setting. Minimum input span between any two inputs is 10 Hz. An error message will appear if the input span is too small.
Calibration: (PD6363) May be calibrated using K-factor, internal calibration, or by applying an external calibration signal.
Input Impedance: (PD6262) Voltage ranges: greater than 500 K Ω. Current ranges: 50 - 100 Ω (depending on resettable fuse impedance).
Input Overload: (PD6262) Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
K-Factor: (PD6363) Field programmable K-factor converts input pulses to rate in engineering units. May be programmed from 0.00001 to 999,999 pulses/unit.
Filter: (PD6363) Programmable contact de-bounce filter: 40 to 999 Hz maximum input frequency allowed with low speed filter.
Time Base: (PD6363) Second, minute, hour, or day
Gate: (PD6363) Low gate: 0.1-99.9 seconds, High gate: 2.0-999.9 seconds
F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC, Logic Low: 0 to 1.25 VDC

Dual Rate/Totalizer

Rate Display Indication: 0 to 999999, lead zero blanking.
Total Display & Total Overflow: 0 to 999,999; automatic lead zero blanking. Up to 999,999,999 with total-overflow feature. "oF" is displayed to the left of total overflow.
Total Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd. Total decimal point is independent of rate decimal point. Channel A and B decimal points programmed independently.
Dual Totalizer: Calculates total for channels A and B based on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed. Channel A and B totalizer parameters programmed independently.
Totalizer Rollover: Totalizer rolls over when display exceeds 999,999,999. Relay status reflects the display value.
Total Overflow Override: Program total A or B total reset for automatic with 0.1 second delay and set point 1 for 999,999
Totalizer Alarm Presets: Up to eight, user selectable under setup menu. Any set point can be assigned to channel A or B total or grand total (or C) and may be programmed anywhere in the range of the meter for total alarm indication.
Total & Grand Total Reset: Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications. Channel A and B total and grand total reset parameters programmed independently.
Total Reset Password: Total and grand total passwords may be entered to prevent resetting the total or grand total from the front panel.
Non-Resettable Total: The grand totals can be programmed as non-resettable totals by entering the password "050873". Both channels are set to non-resettable when this password is entered. Caution: Once the Grand Total has been programmed as "non-resettable" the feature cannot be disabled.
Programmable Delay on Release: 0.1 and 999.9 seconds; applied to the first relay assigned to total or grand total. If the meter is programmed to reset total to zero automatically when the preset is reached, then a delay will occur before the total is reset.

Relays

Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads
Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads.
Relay Assignment: Relays may be assigned to channel A or B rate, total, or grand total; channel C; or Modbus control.
Deadband: 0-100% of span, user programmable
High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
Relay Operation: automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), off (disable unused relays), and manual on/off control mode.
Relay Reset: User selectable via front panel buttons, digital inputs, or PC
   1. Automatic reset only (non-latching), when input passes the reset point.
   2. Automatic + manual reset at any time (non-latching).
   3. Manual reset only, at any time (latching).
   4. Manual reset only after alarm condition has cleared (latching).
Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.
Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
Fail-Safe Operation: Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.

Isolated 4-20 mA Transmitter Output

Output Source: Input channels A or B, rate, total, or grand total; channel C; max or min for channel A or B; highest or lowest max or min of A and B; set points 1-8; Modbus input; or manual control mode.
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated: 4.000 to 20.000 = 4-20 mA output
Analog Output Programming: 23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
Accuracy: ±0.1% FS ±0.004 mA
Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ±10%. May be used to power the 4-20 mA output or other devices.
ProVu Series (PD6262/PD6363): All models rated @ 40 mA max.
ProtEX-MAX (PD8 Series): All models @ 25 mA max.
External Loop Power Supply: 35 VDC maximum
Output Loop Resistance:
      Power supply Minimum Maximum
      24 VDC 10Ω 700Ω
      35 VDC (external) 100Ω 1200Ω

Serial Communications

Protocol: Modbus® RTU
Meter Address/Slave ID: 1 - 247
Baud Rate: 300 - 19,200 bps
Transmit Time Delay: Programmable between 0 and 199 ms
Data: 8 bit (1 start bit, 1 or 2 stop bits)
Parity: Even, odd, or none with 1 or 2 stop bits
Byte-to-Byte Timeout: 0.01 - 2.54 seconds
Turn Around Delay: Less than 2 ms (fixed)
Note: Refer to the ProVu Modbus Register Tables for details

Digital I/O Expansion Module

Channels: 4 digital inputs & 4 digital outputs per module
System: Up to 2 modules for a total of 8 inputs & 8 outputs
Digital Input Logic: High: 3 to 5 VDC Low: 0 to 1.25 VDC
Digital Output Logic: High: 3.1 to 3.3 VDC Low: 0 to 0.4 VDC
Source Current: 10 mA maximum
Sink Current: 1.5 mA minimum
+5 V Terminal: To be used as pull-up for digital inputs only

4-Relay Expansion Module

Relays: Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 watts) @ 125/250 VAC for inductive loads.

Dual Analog Output Expansion Module

Outputs: Two passive 4-20 mA analog outputs
Scaling Range: 3.000 to 23.000 mA for any display range

ORDERING INFORMATION

QuickShip Program Eligible Product Blue dot denotes item as a Quick Ship product

ProVu PD6262 Models

Check Stock for All
Model Description Price  
PD6262-6R0 ProVu Dual-Input Analog Flow Rate/Totalizer
No Options
Powered from 85-265 VAC
529.00 Buy Now
PD6262-6R2 ProVu Dual-Input Analog Flow Rate/Totalizer
2 Relays
Powered from 85-265 VAC
574.00 Buy Now
PD6262-6R3 ProVu Dual-Input Analog Flow Rate/Totalizer
4-20 mA Output
Powered from 85-265 VAC
594.00 Buy Now
PD6262-6R4 ProVu Dual-Input Analog Flow Rate/Totalizer
4 Relays
Powered from 85-265 VAC
614.00 Buy Now
PD6262-6R5 ProVu Dual-Input Analog Flow Rate/Totalizer
2 Relays + 4-20 mA Output
Powered from 85-265 VAC
634.00 Buy Now
PD6262-6R7 ProVu Dual-Input Analog Flow Rate/Totalizer
4 Relays + 4-20 mA Output
Powered from 85-265 VAC
679.00 Buy Now
PD6262-7R0 ProVu Dual-Input Analog Flow Rate/Totalizer
No Options
Powered from 12-24 VDC
594.00 Buy Now
PD6262-7R2 ProVu Dual-Input Analog Flow Rate/Totalizer
2 Relays
Powered from 12-24 VDC
634.00 Buy Now
PD6262-7R3 ProVu Dual-Input Analog Flow Rate/Totalizer
4-20 mA Output
Powered from 12-24 VDC
654.00 Buy Now
PD6262-7R4 ProVu Dual-Input Analog Flow Rate/Totalizer
4 Relays
Powered from 12-24 VDC
679.00 Buy Now
PD6262-7R5 ProVu Dual-Input Analog Flow Rate/Totalizer
2 Relays + 4-20 mA Output
Powered from 12-24 VDC
699.00 Buy Now
PD6262-7R7 ProVu Dual-Input Analog Flow Rate/Totalizer
4 Relays + 4-20 mA Output
Powered from 12-24 VDC
739.00 Buy Now
PD6262-6H0 ProVu Dual-Input Analog Flow Rate/Totalizer
No Options
Powered from 85-265 VAC
SunBright Display
629.00 Buy Now
PD6262-6H2 ProVu Dual-Input Analog Flow Rate/Totalizer
2 Relays
Powered from 85-265 VAC
SunBright Display
674.00 Buy Now
PD6262-6H3 ProVu Dual-Input Analog Flow Rate/Totalizer
4-20 mA Output
Powered from 85-265 VAC
SunBright Display
694.00 Buy Now
PD6262-6H4 ProVu Dual-Input Analog Flow Rate/Totalizer
4 Relays
Powered from 85-265 VAC
SunBright Display
714.00 Buy Now
PD6262-6H5 ProVu Dual-Input Analog Flow Rate/Totalizer
2 Relays + 4-20 mA Output
Powered from 85-265 VAC
SunBright Display
734.00 Buy Now
PD6262-6H7 ProVu Dual-Input Analog Flow Rate/Totalizer
4 Relays + 4-20 mA Output
Powered from 85-265 VAC
SunBright Display
779.00 Buy Now
PD6262-7H0 ProVu Dual-Input Analog Flow Rate/Totalizer
No Options
Powered from 12-24 VDC
SunBright Display
694.00 Buy Now
PD6262-7H2 ProVu Dual-Input Analog Flow Rate/Totalizer
2 Relays
Powered from 12-24 VDC
SunBright Display
734.00 Buy Now
PD6262-7H3 ProVu Dual-Input Analog Flow Rate/Totalizer
4-20 mA Output
Powered from 12-24 VDC
SunBright Display
754.00 Buy Now
PD6262-7H4 ProVu Dual-Input Analog Flow Rate/Totalizer
4 Relays
Powered from 12-24 VDC
SunBright Display
779.00 Buy Now
PD6262-7H5 ProVu Dual-Input Analog Flow Rate/Totalizer
2 Relays + 4-20 mA Output
Powered from 12-24 VDC
SunBright Display
799.00 Buy Now
PD6262-7H7 ProVu Dual-Input Analog Flow Rate/Totalizer
4 Relays + 4-20 mA Output
Powered from 12-24 VDC
SunBright Display
839.00 Buy Now

ProVu PD6363 Models

Check Stock for All
Model Description Price  
PD6363-6R0 ProVu Dual-Input Pulse Flow Rate/Totalizer
No Options
Powered from 85-265 VAC
529.00 Buy Now
PD6363-6R2 ProVu Dual-Input Pulse Flow Rate/Totalizer
2 Relays
Powered from 85-265 VAC
574.00 Buy Now
PD6363-6R3 ProVu Dual-Input Pulse Flow Rate/Totalizer
4-20 mA Output
Powered from 85-265 VAC
594.00 Buy Now
PD6363-6R4 ProVu Dual-Input Pulse Flow Rate/Totalizer
4 Relays
Powered from 85-265 VAC
614.00 Buy Now
PD6363-6R5 ProVu Dual-Input Pulse Flow Rate/Totalizer
2 Relays + 4-20 mA Output
Powered from 85-265 VAC
634.00 Buy Now
PD6363-6R7 ProVu Dual-Input Pulse Flow Rate/Totalizer
4 Relays + 4-20 mA Output
Powered from 85-265 VAC
679.00 Buy Now
PD6363-7R0 ProVu Dual-Input Pulse Flow Rate/Totalizer
No Options
Powered from 12-24 VDC
594.00 Buy Now
PD6363-7R2 ProVu Dual-Input Pulse Flow Rate/Totalizer
2 Relays
Powered from 12-24 VDC
634.00 Buy Now
PD6363-7R3 ProVu Dual-Input Pulse Flow Rate/Totalizer
4-20 mA Output
Powered from 12-24 VDC
654.00 Buy Now
PD6363-7R4 ProVu Dual-Input Pulse Flow Rate/Totalizer
4 Relays
Powered from 12-24 VDC
679.00 Buy Now
PD6363-7R5 ProVu Dual-Input Pulse Flow Rate/Totalizer
2 Relays + 4-20 mA Output
Powered from 12-24 VDC
699.00 Buy Now
PD6363-7R7 ProVu Dual-Input Pulse Flow Rate/Totalizer
4 Relays + 4-20 mA Output
Powered from 12-24 VDC
739.00 Buy Now
PD6363-6H0 ProVu Dual-Input Pulse Flow Rate/Totalizer
No Options
Powered from 85-265 VAC
SunBright Display
629.00 Buy Now
PD6363-6H2 ProVu Dual-Input Pulse Flow Rate/Totalizer
2 Relays
Powered from 85-265 VAC
SunBright Display
674.00 Buy Now
PD6363-6H3 ProVu Dual-Input Pulse Flow Rate/Totalizer
4-20 mA Output
Powered from 85-265 VAC
SunBright Display
694.00 Buy Now
PD6363-6H4 ProVu Dual-Input Pulse Flow Rate/Totalizer
4 Relays
Powered from 85-265 VAC
SunBright Display
714.00 Buy Now
PD6363-6H5 ProVu Dual-Input Pulse Flow Rate/Totalizer
2 Relays + 4-20 mA Output
Powered from 85-265 VAC
SunBright Display
734.00 Buy Now
PD6363-6H7 ProVu Dual-Input Pulse Flow Rate/Totalizer
4 Relays + 4-20 mA Output
Powered from 85-265 VAC
SunBright Display
779.00 Buy Now
PD6363-7H0 ProVu Dual-Input Pulse Flow Rate/Totalizer
No Options
Powered from 12-24 VDC
SunBright Display
694.00 Buy Now
PD6363-7H2 ProVu Dual-Input Pulse Flow Rate/Totalizer
2 Relays
Powered from 12-24 VDC
SunBright Display
734.00 Buy Now
PD6363-7H3 ProVu Dual-Input Pulse Flow Rate/Totalizer
4-20 mA Output
Powered from 12-24 VDC
SunBright Display
754.00 Buy Now
PD6363-7H4 ProVu Dual-Input Pulse Flow Rate/Totalizer
4 Relays
Powered from 12-24 VDC
SunBright Display
779.00 Buy Now
PD6363-7H5 ProVu Dual-Input Pulse Flow Rate/Totalizer
2 Relays + 4-20 mA Output
Powered from 12-24 VDC
SunBright Display
799.00 Buy Now
PD6363-7H7 ProVu Dual-Input Pulse Flow Rate/Totalizer
4 Relays + 4-20 mA Output
Powered from 12-24 VDC
SunBright Display
839.00 Buy Now
 

Enclosures

PDA2300 Enclosure Family Enclosure Selection Utility
    Check Stock for
All Enclosures
Model Description Price  
PDA2302 Economical Plastic NEMA 4X Enclosure for 2 Type A, B, C, or E Meters
159.00 Buy Now
PDA2504 Plastic NEMA 4X Enclosure for 4 Type A, B, C, or E Meters
349.00 Buy Now
PDA2505 Plastic NEMA 4X Enclosure for 5 Type A, B, C, or E Meters
369.00 Buy Now
PDA2506 Plastic NEMA 4X Enclosure for 6 Type A, B, C, or E Meters
389.00 Buy Now
PDA2507 Plastic NEMA 4X Enclosure for 7 Type A, B, C, or E Meters
494.00 Buy Now
PDA2508 Plastic NEMA 4X Enclosure for 8 Type A, B, C, or E Meters
534.00 Buy Now
PDA2509 Plastic NEMA 4X Enclosure for 9 Type A, B, C, or E Meters
574.00 Buy Now
PDA2510 Plastic NEMA 4X Enclosure for 10 Type A, B, C, or E Meters
604.00 Buy Now
PDA2512 Plastic NEMA 4X Enclosure for 2 Type A, B, C, or E Meters
374.00 Buy Now
PDA2604 Stainless Steel NEMA 4X Enclosure for 4 Type A,B, C or E Meters
859.00 Buy Now
PDA2605 Stainless Steel NEMA 4X Enclosure for 5 Type A,B, C or E Meters
919.00 Buy Now
PDA2606 Stainless Steel NEMA 4X Enclosure for 6 Type A,B, C or E Meters
979.00 Buy Now
PDA2704 Steel NEMA 4 Enclosure for 4 Type A, B, C, or E Meters
444.00 Buy Now
PDA2704-1 Steel NEMA 4 Enclosure for 1 Type A, B, C or E Meters
384.00 Buy Now
PDA2704-2 Steel NEMA 4 Enclosure for 2 Type A, B, C or E Meters
404.00 Buy Now
PDA2705 Steel NEMA 4 Enclosure for 4 Type A, B, C or E Meters
494.00 Buy Now
PDA2706 Steel NEMA 4 Enclosure for 5 Type A, B, C or E Meters
554.00 Buy Now
PDA2713 Steel NEMA 4X Enclosure for 3 Type A, C, or E Meters + 1 Type D Meter
469.00 Buy Now
PDA2812 Low-Cost Plastic NEMA 4X Enclosure for 2 Meters (Any type)
159.00 Buy Now
PDA2821 Low-Cost Plastic NEMA 4X Enclosure for 1 Type D Meter + 1 Type A, B, C or E Meter
184.00 Buy Now
PDA3407 Plastic NEMA 4X Enclosure for Any One 1/8 DIN Meter
179.00 Buy Now
  

Accessories

    Check Stock for
All Accessories
Model Description Price  
PDA1002   ProVu DIN Rail Mounting Kit for Two Modules
13.00
PDA1004   ProVu 4 Relays Expansion Module
83.00
PDA1011   ProVu Expansion Module: Dual Isolated Analog Output Expansion Module (ProVu Models: PD6060, PD6080, PD6081, PD6088, PD6089, PD6262, and PD6363 only)
99.00
PDA1044   ProVu 4 Digital Inputs & 4 Outputs Module
36.00
PDA1200   ProVu Meter Copy Cable, 3' (0.9 m)
10.00
PDA1232   ProVu RS-232 Serial Adapter
82.00
PDA1485   ProVu RS-485 Serial Adapter
82.00
PDA7485-I   RS-232 to RS-422/485 Isolated Converter
179.00
PDA7485-N   RS-232 to RS-422/485 Non-Isolated Converter
144.00
PDA8008   ProVu USB Serial Adapter
39.00
PDA8232-N   USB to RS-232 Converter
51.00
PDA8485-I   USB to RS-422/485 Isolated Converter
196.00
PDA8485-N   USB to RS-422/485 Non-Isolated Converter
164.00
PDX6901   Suppressor (snubber): 0.01µF/470Ω,
10.00


DOCUMENTATION

Precision Digital Return User Form

Previously registered users of the site can access documentation by entering their email address and password below and selecting Login. Unregistered users can access documentation by selecting New User and entering registration information.

Email:
Password:



Add New User Information Forgot Password




Precision Digital Corporation Since 1974 ISO 9001 Certified
Precision Digital Site Map Precision Digital Privacy Policy Precision Digital Copyright 2000-2013
MeterView Pro Link