Vigilante Annunciator Alarm Sequence |
FULL SEQUENCE DESCRIPTIONS
The following section describes the operation of the various sequences available in the Vigilante® alarm annunciator.
Features
Acknowledge Pushbutton: Momentary alarms will not clear until the alarmed channels have been acknowledged with the ACK pushbutton. This will also reset the first out indication. Used in all ISA sequences.
Automatic Reset: Acknowledged momentary alarms will clear automatically when the inputs return to normal. The automatic reset is present in all automatic (A) sequences.
First-Out Indication: The sequence provides a distinct visual indication for the first channel to alarm.
First-Out Reset Pushbutton: Resets the first-out display and assigns the first-out channel to display as a subsequent alarm without any other changes to the sequence. The next alarm input will be a new first-out alarm. Used only in sequence F3A.
Reset Pushbutton: Acknowledged momentary alarms will only clear when reset with the RESET pushbutton. Used in any manual reset (M) sequence.
Sequence Condition Descriptions
The following terms are used in describing the sequence behavior in the following tables:
Alert: The input is in alarm state, and the channel has not been acknowledged with the ACK pushbutton.
Acknowledge: The alarm state is acknowledged with the ACK pushbutton. This will restart the first-out indication.
First Out Reset (F3A Only): The RESET pushbutton is used to reset the first-out indication only.
Normal: Inputs are in the normal state.
LED Condition Descriptions
1st Pt: Indicates the behavior of the first-out channel only.
Next Pt: The behavior of subsequent alarm channels; channels that enter the alarm state after the first-out alarm.
FISA SEQUENCE A
Acknowledge Pushbutton and Automatic Reset
Momentary Alarm
| Condition |
LED |
Horn |
Normal
|
Off
|
Off
|
Alert
|
Flash
|
On
|
Normal
|
Flash
|
On
|
ACK Pushbutton
|
Acknowledge
|
Off
|
Off
|
Maintained Alarm
| Condition |
LED |
Horn |
Normal
|
Off
|
Off |
Alert
|
Flash
|
On
|
ACK Pushbutton
|
Acknowledge
|
Steady
|
Off
|
Normal
|
Off
|
Off
|
Sequence A Switch Positions
Sequence A Flowchart
Relay Operation
For complete details on relay function, see page 24 in the instruction manual
Relay 1: Operation Relay 1 enters alarm state when there is a new alarm. This relay will clear when the alarms are acknowledged.
Relay 2: Operation Relay 2 enters alarm state when any channel displays in alarm state. This relay will clear when all indication LEDs are cleared.
ISA SEQUENCE F2A
First-Out Indication with Acknowledge Pushbutton and Automatic Reset
Momentary Alarm
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Flash
|
Steady
|
On
|
Normal
|
Flash
|
Steady
|
On
|
ACK Pushbutton
|
Acknowledge
|
Off
|
Off
|
Off
|
Maintained Alarm
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Flash
|
Steady
|
On |
ACK Pushbutton
|
Acknowledge
|
Steady
|
Steady
|
Off
|
Normal
|
Off
|
Off
|
Off
|
Sequence F2A Switch Positions
Sequence F2A Flowchart
ISA SEQUENCE F1A
First-Out Indication with Acknowledge Pushbutton, No Lock-In of Subsequent Alarms, and Automatic Reset
Momentary Alarm
| Condition |
LED |
Horn
|
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Flash
|
Steady
|
On
|
Normal
|
Flash
|
Off
|
On
|
ACK Pushbutton
|
Acknowledge
|
Off
|
Off
|
Off
|
Maintained Alarm
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Flash
|
Steady
|
On
|
ACK Pushbutton
|
Acknowledge
|
Steady
|
Steady
|
Off
|
Normal
|
Off
|
Off
|
Off
|
Sequence F1A Switch Positions
Sequence F1A Flowchart
ISA SEQUENCE F3A
First-Out Indication with Acknowledge Pushbutton, Automatic Reset, and First-Out Reset Pushbutton
Momentary Alarm (RESET before ACK)
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Intermittent Flash
|
Fast Flash
|
On
|
Normal
|
Intermittent Flash
|
Fast Flash
|
On |
RESET Pushbutton
|
1st Out Reset
|
Fast Flash
|
Fast Flash
|
On
|
ACK Pushbutton
|
Acknowledge
|
Off
|
Off
|
Off
|
Momentary Alarm (ACK before RESET)
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Intermittent Flash
|
Fast Flash
|
On
|
Normal
|
Intermittent Flash
|
Fast Flash
|
On
|
ACK Pushbutton
|
Acknowledge
|
Slow Flash
|
Off
|
Off
|
RESET Pushbutton
|
Reset
|
Off
|
Off
|
Off
|
Maintained Alarm (RESET before ACK)
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Intermittent Flash
|
Fast Flash
|
On
|
RESET Pushbutton
|
1st Out Reset
|
Fast Flash
|
Fast Flash
|
On
|
ACK Pushbutton
|
Acknowledge
|
Steady
|
Steady
|
Off
|
Normal
|
Off
|
Off
|
Off
|
Maintained Alarm (ACK before RESET)
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Intermittent Flash
|
Fast Flash
|
On
|
ACK Pushbutton
|
Acknowledge
|
Slow Flash
|
Steady
|
Off
|
RESET Pushbutton
|
1st Out Reset
|
Steady
|
Steady
|
Off
|
Normal
|
Off
|
Off
|
Off
|
Sequence F3A Switch Positions
Sequence F3A Flowchart
INPUT FOLLOWER INDICATION
| Simple Indication |
| Condition |
LED |
Horn
|
| Normal |
Off
|
Off
|
Alert
|
Steady
|
On
|
Normal
|
Off
|
Off
|
ISA SEQUENCE M
Acknowledge and Reset Pushbuttons
Momentary Alarm
| Condition |
LED |
Horn |
Normal
|
Off
|
Off |
Alert
|
Flash
|
On
|
Normal
|
Flash
|
On
|
ACK Pushbutton
|
Acknowledge
|
Steady
|
Off
|
RESET Pushbutton
|
Reset
|
Off
|
Off
|
Maintained Alarm
| Condition |
LED |
Horn |
Normal
|
Off
|
Off
|
Alert
|
Flash
|
On
|
ACK Pushbutton
|
Acknowledge
|
Steady
|
Off
|
| Normal |
Steady
|
Off
|
| RESET Pushbutton |
Normal
|
Off
|
Off
|
Sequence M Switch Positions
Sequence M Switch Flowchart
ISA Sequence F1M
First-Out Indication with Acknowledge and Reset Pushbuttons, and No-Lock-In of Subsequent Alarms
Momentary Alarm
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Flash
|
Steady
|
On
|
Normal
|
Flash
|
Steady
|
On
|
RESET Pushbutton
|
Reset
|
Flash
|
Off
|
On
|
ACK Pushbutton
|
Acknowledge
|
Steady
|
Off
|
Off
|
RESET Pushbutton
|
Normal
|
Off
|
Off
|
Off
|
Maintained Alarm
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Flash
|
Steady
|
On
|
RESET Pushbutton
|
Alert
|
Flash
|
Steady
|
On
|
ACK Pushbutton
|
Acknowledge
|
Steady
|
Steady
|
Off
|
Normal
|
Steady
|
Steady
|
Off
|
| RESET Pushbutton |
Normal
|
Off
|
Off
|
Off
|
Sequence F1M Switch Positions
Sequence F1M Flowchart
ISA SEQUENCE F2M
First-Out Indication with Acknowledge and Reset Pushbuttons
Momentary Alarm
| Condition |
LED |
Horn |
|
1st Pt
|
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Flash
|
Steady
|
On
|
Normal
|
Flash
|
Steady
|
On
|
ACK Pushbutton
|
Acknowledge
|
Steady
|
Steady
|
Off
|
RESET Pushbutton
|
Reset
|
Off
|
Off
|
Off
|
Maintained Alarm
| Condition |
LED |
Horn |
|
1st Pt |
Next Pt |
|
Normal
|
Off
|
Off
|
Off
|
Alert
|
Flash
|
Steady
|
On
|
ACK Pushbutton
|
Acknowledge
|
Steady
|
Steady
|
Off
|
Normal
|
Steady
|
Steady
|
Off
|
RESET Pushbutton
|
Normal
|
Off
|
Off
|
Off
|
Sequence F2M Switch Positions
Sequence F2M Flowchart
|